AIR FOR COMBUSTION AND VENTILATION

Continued

Example 2: Locating Heater in Confined (Closed) Area

NOTICE

A confined area has an air volume of less than 50 cubic feet for each 1000 BTU/Hr input rating of all appliances in the area (cubic feet equals length x width x height of area). Include adjoining rooms only if there are no doors between the rooms.

If you install this heater in a confined area, you must provide additional fresh air.

Ventilating Confined Area

This fresh air would come from an adjoining open area or outdoors.

WARNING

WARNING ICON

G 001

The adjoining open area must have enough fresh, outside air ventilation to supply any appliance in that area plus the confined area. Follow instructions under Example 1: Locating Heater in Unconfined (Open) Area, page 18 to make sure fresh air ventilation is adequate.

When ventilating to an adjoining open area, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two areas. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1. It lists fresh-air requirements for fuel-burning appliances.

Ventilation

Grills into

Closet for

Hot Water

Heater

12"

Ventilation Grills

Connecting Two Rooms to Meet Unconfined Space

20

12"

Recommended

Fresh Air Duct into Crawl Space in Furnace Area or in

Closet with Water Heater

Figure 16 - Ventilation Air from Inside Building

After providing ventilation between rooms, check for draft hood spillage (see Draft Hood Spillage Test, page 18). If draft hood spillage still occurs, provide more ventilation between rooms or provide permanent ventilation from outdoors. See Providing Permanent Fresh-Air Ventilation, page 19.

100792

Page 20
Image 20
Desa CGR35NA, CGR65NA, CGR50BNA, CGR50NA, CGR65BNA installation manual Example 2 Locating Heater in Confined Closed Area