CHECKING GAS CONNECTIONS

INSTALLATION

Connecting Equipment shutoff Valve To Heater Control (Cont.) Checking Gas Connections

19

INSTALLATION

Continued

2.Route flexible gas line, included, from fireplace control to equipment shutoff valve through side or rear access holes in outer casing.

3.Apply pipe joint sealant lightly to male threads of gas connec- tor attached to flexible gas line/equipment shutoff valve (see Figure 32).

Pressure Testing gas Supply Piping system CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings (Thermostat-Controlled Mod- els Only).

Manual background CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or fittings (Remote-Ready Models Only).

4.Check all gas connections for leaks. See Checking Gas Con- nections.

5.Replace branch support back into fireplace. Feed flexible gas line into fireplace base area while replacing branch support. Make sure the entire flexible gas line is in fireplace base area. Reat- tach branch support to fireplace with screws removed in step 1.

CHECKING GAS CONNECTIONS

Manual background WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Manual background CAUTION: Make sure external regulator has been installed between propane/LP supply and fireplace. See guidelines under Connecting to Gas Supply, pages 17 and 18.

Pressure Testing gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect appliance with its appliance main gas valve (control

valve) and equipment shutoff valve from gas supply piping sys-

tem. Pressures in excess of 1/2 psig will damage heater regulator.

To Gas Regulator (Thermostat- Controlled Models) or Control Valve (Remote-Ready Models)

Manual background

Flexible Gas Line from Fireplace Gas Regulator Provided With Fireplace

Equipment

Shutoff Valve

PROPANE/LP

 

 

To External

 

Regulator

 

NATURAL

 

To Gas Supply

2.

Cap off open end of gas pipe where equipment shutoff valve

 

was connected.

3.

Pressurize supply piping system by either opening propane/LP sup-

 

ply tank valve for propane/LP gas or opening main gas valve lo-

 

cated on or near gas meter for natural gas, or using compressed air.

4.

Check all joints of gas supply piping system. Apply noncorrosive

 

leak detection fluid to all joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment shutoff valve to gas sup-

 

ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP sup- ply tank valve for propane/LP gas or opening main gas valve lo- cated on or near gas meter for natural gas, or using compressed air.

Figure 32 - Attaching Flexible Gas Line to Equipment Shutoff Valve