INSTALLING

CHECKING GAS CONNECTIONS

HEATER

 

WARNING ICONG 001 WARNING

Continued

 

Test all gas piping and connections for leaks after install-

 

 

 

ing or servicing. Correct all leaks at once.

 

 

 

 

 

 

 

 

 

 

 

WARNING ICONG 001 WARNING

 

 

Never use an open flame to check for a leak. Apply a

 

 

 

mixture of liquid soap and water to all joints. Bubbles

 

 

forming show a leak. Correct all leaks at once.

 

 

 

 

 

 

 

 

 

WARNING ICONG 001 CAUTION

 

 

Make sure external regulator has been installed between

 

 

 

propane supply and heater. See guidelines under Con-

 

 

necting to Gas Supply, page 11.

 

 

 

 

 

Pressure Testing Gas Supply Piping System

Test Pressures In Excess of 1/2 PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply pipe. Pressures in excess of 1/2 PSIG will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening propane supply tank valve.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Re-connect heater and manual shutoff valve to gas supply. Check re-connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 8).

2.Pressurize supply piping system by either using compressed air or opening propane supply tank valve.

3.Check all joints from propane supply tank to manual shutoff valve. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Figure 8).

2.Open propane supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve on heater. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 21 through 23). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 23).

PO On Position

Off Position

 

Continued

 

Figure 8 - Manual Shutoff Valve

13

 

 

 

 

100793

Page 13
Image 13
Desa Tech CGR50PA, CGR65BPA, CGR35PA, CGR50BPA, CGR65PA Checking GAS Connections, Pressure Testing Gas Supply Piping System

CGR50BPA, CGR65BPA, CGR65PA, CGR35PA, CGR50PA specifications

Desa Tech's CGR series, including the CGR50PA, CGR35PA, CGR65PA, CGR65BPA, and CGR50BPA, represents a cutting-edge line of gas logs designed for efficiency, reliability, and user-friendly operation. Each model combines modern engineering with top-tier technologies to deliver warmth and aesthetic appeal to any living space.

The CGR50PA is known for its compact yet powerful heating capabilities, offering a maximum input of 50,000 BTUs. This model is ideal for smaller rooms, providing consistent warmth without taking up excessive space. Its advanced burner technology ensures a realistic flame appearance, enhancing the ambiance of any setting.

The CGR35PA stands out with its lower BTU output of 35,000, making it perfect for cozy spaces or homes looking for a supplemental heating source. This model emphasizes energy efficiency, utilizing a state-of-the-art control system that optimizes fuel consumption while maintaining performance and comfort.

In contrast, the CGR65PA is designed for larger areas, boasting an impressive output of 65,000 BTUs. This model features a dual burner system, which not only increases heat distribution but also adds to the visual appeal with varying flame heights. Its robust construction guarantees durability, and an easy-to-use remote control provides added convenience.

The CGR65BPA variant further increases efficiency with its built-in blower system, which circulates warm air throughout the room, ensuring even heating. This model is particularly useful in expansive living areas where traditional heating methods may fall short. Its innovative safety features, including an oxygen depletion sensor, provide peace of mind for users.

Lastly, the CGR50BPA combines the advantages of its siblings, offering a balanced heating solution for medium-sized rooms. With a blower and adjustable thermostat, this model allows users to tailor their heating experience. Each unit in the CGR series is compatible with natural gas or propane, maximizing versatility based on individual preferences or regional availability.

Overall, the Desa Tech CGR series epitomizes modern gas log technology, focusing on performance, efficiency, and safety, making them an excellent choice for anyone seeking reliable and attractive heating solutions.