AIR FOR

COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1and 2, Figure 8). You can also remove door into adjoining room (see op- tion 3, Figure 8). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

OWNER'S MANUAL

 

Ventilation Grills

Ventilation

Into Adjoining Room,

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option3

 

©

1

S

_I'WARNING: Rework work-

sheet, adding the space of the Figure 8 - Ventilation Air from Inside Building adjoining unconfined space. The

combined spaces must have enough fresh air to supply all appliances In both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces

include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANSI

Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a

thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Outlet

Air

To Attic

To

Crawl

Space

Inlet

Air

Inlet Air

Ventilated

 

Crawl Space

Figure 9 - Ventilation Air from Outdoors

_o_

7

Page 7
Image 7
Desa Tech RFP30T installation manual Ventilation AIR, Ventilation Air From Inside Building, To Attic, Space