Installation

J11 Annunciator Outputs

18.1 Description

The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or conditions occurring on the system. Annunciator outputs do not provide a voltage but instead switch- to-grounda voltage from another source and are rated at a maximum 30 VDC @ 50mA. The outputs can respond to any of the conditions listed in the Description section of Dry Contact Relay Outputs.

18.2 Model 300 Harness Wiring

Access the open collector outputs by installing DMP 300 Harness on the 4-pin header labeled J11. The output locations are shown below.

Note: For UL applications, devices connected to the outputs must be located within the same room as the panel.

Output

Color

Wire

Output

Color

Wire

3

Red

1

5

Green

3

4

Yellow

2

6

Black

4

18.3 Model 860 Relay Module

Connect a Model 860 Relay Module to the J11 on the XR2500F panel to provide relays for outputs 3-6. Use these relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power terminal 7. The module includes one relay and provides three additional sockets for expansion of up to four relays. Mount the 860 inside the panel enclosure using the 3-hole pattern and plastic standoffs. Refer to the 860 Module Install Sheet (LT-0484) as needed.

Model 305 Relay Contact Rating: 1 Amp at 30 VDC (allows .35 power factor)

J23 6-Pin Header

19.1 Description

The XR2500F Command Processor™ panel supports RS-232, LX-Bus and Wireless Bus expansion operation. These operations cannot function at the same time. Install a jumper on one pair of J23 headers to indicate how the panel is programmed to operate. Refer to the table below when installing a jumper on J23. When a jumper is installed or moved on the 6-pin header, briefly reset the panel using the J16 jumper to activate the selected operation.

J23 6-Pin Header

Letter Operation

RStandard RS-232

LLX-Bus

XWireless Bus

J21

J23

R

L

X

 

LEDs

 

RS-232

Xmit

 

J22

Rec

Overcurrent

 

LX

 

(OVC) LED

Figure 14: J23 6-Pin Header