Compliance

Control Units for Fire-Protective Signaling Systems

ANSI/UL 864, NFPA 72

35.1 Power Supply

For listed installations, the total current combined from Auxiliary and Bell Power cannot exceed:

1.2Amps with a 56 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell Combined total current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.

35.2Zone Restoral Reports

The Restoral Reports option must be selected as YES or Disarm. .

35.3 Power Fail Delay

The Power Fail Delay option must be selected as required by the service of the panel. For Central Station or Remote Station service: 1.

35.4 Sprinkler Supervisory

Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The last three characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module must be used on all sprinkler supervisory systems.

35.5 DACT Systems

Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893A Dual Phone Line Module is used to provide two phone line connections to the system. The 2ND Phone Line communication option must be selected as DD.

Two different phone numbers must be programmed for digital communication. The Test Time option must be programmed so that the XR2500F sends a report every 24 hours.

35.7 Local Protective Signaling Systems

The DMP Model 865, 866, or 867 Notification Circuit Module must be used on the bell circuit for detection of shorts and grounds. See this guide for wiring diagrams. Any burglary or other off premises communication must be done with the Model 893A Dual Phone Line Module. For local commercial fire installations, the 893A is required.

35.8 Remote Station Protective Signaling Systems

You must provide 60 hours of standby battery. See this guide for standby battery calculations. Two Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127 Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.

35.9 Fire Protective Signaling Systems using Internet/Intranet Networks

The XR2500F panel must be programmed as described below for Fire Protective Signaling Systems using NET Communication Type.

• SUB CODE must be programmed as YES

• FAIL TIME must be programmed as 5

• CHECKIN must be programmed as 3 • SEND COMM TRBL must be programmed as YES

35.10Combination Systems

For combination fire and burglary systems, powered burglary devices (PIR, Glassbreak, etc.) must be powered from a separate listed power supply (DMP Model 505-12). This requirement is not needed for non- powered burglary devices (door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary Devices in this document.

For combination fire and burglary systems, burglary sounding devices such as sirens and bells must be energized using panel relays, 860 relays, or 716 relays. Programming the output to activate the relay must occur using the Burglary Bell Output option in Area Information or by the Alarm Action output option of Zone Information. The Burglary Bell Action option of the panel Bell Options must be programmed as None.

35.11 Remote Annunciators

At least one Model 630F Remote Annunciator must be used on the system. All fire alarms, fire troubles and supervisory alarms or troubles must be annunciated only on the 630F. All burglary alarms or troubles must only be annunciated on non-fire keypads. See Status List options of the XR500 Series Programming Guide (LT-0679).

XR2500F Installation Guide

Digital Monitoring Products

37

Page 45
Image 45
DMP Electronics XR2500F manual Power Supply, Zone Restoral Reports, Power Fail Delay, Sprinkler Supervisory, Dact Systems

XR2500F specifications

The DMP Electronics XR2500F is an advanced and versatile electronic device designed to cater to a wide range of applications including industrial automation, robotics, and smart home technologies. Known for its robust performance and reliable functionalities, the XR2500F stands out as a leading option in the market.

One of the main features of the XR2500F is its powerful processing unit, which ensures efficient handling of complex tasks and data processing. With a clock speed of up to 2.5 GHz, the device is capable of multitasking, enabling users to run multiple applications simultaneously without compromising performance. This makes the XR2500F an ideal choice for applications that require real-time data processing and analysis.

The XR2500F is equipped with an extensive array of connectivity options, including Wi-Fi, Bluetooth, and Ethernet capabilities. This allows for seamless integration with various devices and networks. The wireless options facilitate easy communication with cloud services and other IoT devices, making it suitable for smart home automation systems, where synchronization and control are critical.

In terms of memory, the XR2500F offers significant storage capacity, with options that can accommodate up to 64GB of RAM and 512GB of flash storage. This ample memory ensures that users can store large amounts of data and run memory-intensive applications without experiencing slowdowns. Additionally, the device supports expandable memory options, allowing for future upgrades to meet growing demands.

The XR2500F also incorporates advanced security technologies to protect sensitive data. Features like end-to-end encryption and secure boot processes safeguard against unauthorized access and data breaches. This is particularly important in industrial settings where data integrity is critical for operational safety.

Another remarkable characteristic of the XR2500F is its energy efficiency. Designed with the latest power management technologies, the device minimizes energy consumption while maximizing performance. This not only reduces operational costs but also aligns with green technology initiatives.

Overall, the DMP Electronics XR2500F is a high-performance electronic device that combines powerful processing, extensive connectivity, robust memory, enhanced security, and energy efficiency. Its versatility and reliability make it a preferred choice for professionals seeking innovative solutions in automation and control systems.