Wiring Diagrams
39.5 867 Class B Style W Notification Appliance Circuit
To initiating zone
DMP Model 867
30mA @ 12 VDC
The 867 must have its
own independent
address ranging from
500 to 999. A
Supervisory zone must be programmed into the XR500 Series to properly supervise each module.
Bell Relay
Address
Supervisory
Address
| Normal/Silence Switch |
| |
| Ground Fault LED | Model 310 | |
| 1K EOL | ||
| Bell Trouble LED | ||
|
| ||
| Bell In + | 1 |
|
| Bell In - | 2 |
|
| Bell Out + | 3 |
|
| Bell Out - | 4 |
|
| Bell Trouble | 5 |
|
| Bell Trouble | 6 |
|
| PWR Mon. 7 |
| |
| Mon. RTN 8 |
| |
TENS | ONES |
| Bell Ring Style (Steady) |
|
|
| |
TENS | ONES |
| Power Supply Monitor LED |
|
|
| Data LED |
Auxiliary Power Supply must be Listed for Fire Protective Signaling Service. Power Supplies must have battery backup.
J6 | ||
12 VDC @ 5 Amps | ||
Supply | ||
+ DC - | ||
|
Model 308
10K EOL
Only one notification appliance may be used when not using a sync module.
Listed, Polarized
Notification Appliances
See the Notification Appliance section
for a list of appliances.
Green |
| Red | Battery AC | Batt |
LED |
| LED | ||
AC | J2 | DC | J3 Start Trouble | Trouble |
|
|
|
| J4 |
| AC |
| + BAT - |
|
The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list.
39.6 867 Class B Style W Multiple Notification Appliance Circuit
To initiating zone
DMP Model 867 |
| Normal/Silence Switch |
| |
30mA @ 12 VDC |
| Ground Fault LED | Model 310 | |
|
| 1K EOL | ||
|
| Bell Trouble LED | ||
|
|
| ||
The 867 must have its |
| Bell In + | 1 |
|
own independent |
|
| ||
| Bell In - | 2 |
| |
address ranging from |
|
| ||
| Bell Out + | 3 |
| |
500 to 999. A |
|
| ||
|
|
|
| |
Supervisory zone must |
| Bell Out - | 4 |
|
be programmed into the |
| Bell Trouble | 5 |
|
panel to properly |
| Bell Trouble | 6 |
|
supervise each module. |
| PWR Mon. 7 |
| |
|
|
| ||
|
| Mon. RTN 8 |
| |
Bell Relay | TENS | ONES |
| Bell Ring Style (Steady) |
|
|
| ||
|
|
|
| |
Address |
|
|
|
|
Supervisory | TENS | ONES |
| Power Supply Monitor LED |
|
|
| ||
Address |
|
|
| Data LED |
|
Auxiliary Power Supply must be Listed for Fire Protective Signaling Service. Power Supplies must have battery backup.
When using an SM Sync Module, the maximum current is 3 Amps.
| J6 | |
12 VDC @ 5 Amps | ||
Supply | ||
+ DC - | ||
|
Green |
| Red | Battery AC | Batt |
LED |
| LED | ||
AC | J2 | DC | J3 Start Trouble | Trouble |
|
|
|
| J4 |
| AC |
| + BAT - |
|
The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list.
| Sync module required when using multiple notification appliances |
| Model 308 |
| 10K EOL |
| Listed, Polarized Notification Appliances |
| See the Notification Appliance section for a list of appliances. |
XR2500F Installation Guide | Digital Monitoring Products |