DMP Electronics XR2500F manual 39.5 867 Class B Style W Notification Appliance Circuit

Models: XR2500F

1 60
Download 60 pages 7.4 Kb
Page 51
Image 51

Wiring Diagrams

39.5 867 Class B Style W Notification Appliance Circuit

To initiating zone

DMP Model 867

30mA @ 12 VDC

The 867 must have its

own independent

address ranging from

500 to 999. A

Supervisory zone must be programmed into the XR500 Series to properly supervise each module.

Bell Relay

Address

Supervisory

Address

 

Normal/Silence Switch

 

 

Ground Fault LED

Model 310

 

1K EOL

 

Bell Trouble LED

 

 

 

Bell In +

1

 

 

Bell In -

2

 

 

Bell Out +

3

 

 

Bell Out -

4

 

 

Bell Trouble

5

 

 

Bell Trouble

6

 

 

PWR Mon. 7

 

 

Mon. RTN 8

 

TENS

ONES

 

Bell Ring Style (Steady)

 

 

 

TENS

ONES

 

Power Supply Monitor LED

 

 

 

Data LED

Auxiliary Power Supply must be Listed for Fire Protective Signaling Service. Power Supplies must have battery backup.

505-12 Power

J6

12 VDC @ 5 Amps

Supply

+ DC -

 

LX-Bus Wiring

Model 308

10K EOL

Only one notification appliance may be used when not using a sync module.

Listed, Polarized

Notification Appliances

See the Notification Appliance section

for a list of appliances.

Green

 

Red

Battery AC

Batt

LED

 

LED

AC

J2

DC

J3 Start Trouble

Trouble

 

 

 

 

J4

 

AC

 

+ BAT -

 

The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list.

39.6 867 Class B Style W Multiple Notification Appliance Circuit

To initiating zone

DMP Model 867

 

Normal/Silence Switch

 

30mA @ 12 VDC

 

Ground Fault LED

Model 310

 

 

1K EOL

 

 

Bell Trouble LED

 

 

 

The 867 must have its

 

Bell In +

1

 

own independent

 

 

 

Bell In -

2

 

address ranging from

 

 

 

Bell Out +

3

 

500 to 999. A

 

 

 

 

 

 

Supervisory zone must

 

Bell Out -

4

 

be programmed into the

 

Bell Trouble

5

 

panel to properly

 

Bell Trouble

6

 

supervise each module.

 

PWR Mon. 7

 

 

 

 

 

 

Mon. RTN 8

 

Bell Relay

TENS

ONES

 

Bell Ring Style (Steady)

 

 

 

 

 

 

 

Address

 

 

 

 

Supervisory

TENS

ONES

 

Power Supply Monitor LED

 

 

 

Address

 

 

 

Data LED

LX-Bus Wiring

SM-12/24 Module

 

Auxiliary Power Supply must be Listed for Fire Protective Signaling Service. Power Supplies must have battery backup.

When using an SM Sync Module, the maximum current is 3 Amps.

505-12 Power

J6

12 VDC @ 5 Amps

Supply

+ DC -

 

Green

 

Red

Battery AC

Batt

LED

 

LED

AC

J2

DC

J3 Start Trouble

Trouble

 

 

 

 

J4

 

AC

 

+ BAT -

 

The Auxiliary Power Supply and Notification Circuit Module trouble contact zone must be programmed as a Supervisory Type zone and must be selected for display in the keypad status list.

 

Sync module required when using multiple notification appliances

 

Model 308

 

10K EOL

 

Listed, Polarized Notification Appliances

 

See the Notification Appliance section for a list of appliances.

XR2500F Installation Guide

Digital Monitoring Products

43

Page 51
Image 51
DMP Electronics XR2500F manual 39.5 867 Class B Style W Notification Appliance Circuit, To initiating zone