Introduction
Introduction
1.1Overview
The DMP XR2500F Addressable Fire Alarm Control Panel (FACP) is an expandable 24 VDC Fire Alarm Control with
•574 programmable inputs and outputs for commercial and industrial fire alarm service.
•Eight
•Two
Connect a 12 or 24 VDC regulated, power limited power supply listed for Fire Protective Signaling Systems to distribute notification appliance power between the two class B style W NAC outputs. Additional NAC outputs can be added with conventional supervision modules or addressable power supply/boosters. Addressable smoke detectors and input modules round out the XR2500F to deliver a truly flexible and expansive fire detection and notification system. The Fire Alarm Control Panel is shipped
The enclosure dimensions are as follows: 32” H x 14.5” W x 4” D. The lid adds about 0.5” to each side.
1.2System Components
The XR2500F FACP consists of the following
• One Model XR2500F Command Processor panel | • | One Model 893A Dual Phone Line module | |
• Two Model 866 Class B Style W NAC modules | • | One Model 630F PCB and membrane switch | |
• | One 16 VAC, 56 VA transformer | • | Two Model 305 |
• | One Model 481 Zone Expansion Interface Card | • | One Metal Backplate |
1.3Power Specifications
Transformer Input: Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Standby Battery: | 12 | VDC, 1.0 Amps Max. charging current |
Auxiliary: | 12 | VDC output at 1.0 Amp Max* |
Bell Output: | 12 | VDC at .7 Amp Max* |
Note: The combined Auxiliary and Bell outputs total cannot exceed 1.9 Amps with a 56 VA Transformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
*For Commercial Fire installations, see the Compliance Instructions section.
1.4Communication
893A Dual Phone Line Module with phone line supervision
Can operate as a local panel
1.5Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8). Connect to 869 Class A module for burglary applications. Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10).
Note: Use the supplied DMP Model 311 1k Ohm and DMP Model 301 3.3k Ohm resistors.
1.6Keypad Bus
You can connect up to 15 of the following supervised keypads and expansion modules to the keypad bus:
•Alphanumeric Fire Command Centers or keypads
•Four- and/or
•
•Access control modules
XR2500F Installation Guide | Digital Monitoring Products |
1