DMP Electronics XR2500F manual Wiring Diagrams, Prewired 866 Modules with NAC Extender

Models: XR2500F

1 60
Download 60 pages 7.4 Kb
Page 48
Image 48

Compliance

Wiring Diagrams

39.1 Prewired 866 Modules with NAC Extender

Prewired to XR2500F panel

Normal/Silence Switch

1 AUX PWR

2 GND

3 Alarm In

4 Bell PWR In

5 Bell Out +

 

 

 

 

Model 310

 

Model 310

1K EOL

 

 

1K EOL

DMP Model 866 45mA @ 12 VDC

The 866 Notification

Appliance Circuit

Module in alarm draws

up to 31mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input.

See the 866

Installation (LT-0059)

6 Bell Out -

7 Bell Trouble

8 Bell Trouble

Normal/Silence Switch

1 AUX PWR

2 GND

3 Alarm In

4 Bell PWR In

5 Bell Out +

6 Bell Out -

7 Bell Trouble

8 Bell Trouble

Note: Terminals 3 and 4 jumper together to supply Bell Power from the panel

PowerPath NAC Extender

Models

PS-8

PS-8E

PS-6

PS-6E

See PowerPath installation for

detailed connection

instructions

The Bell Output programming for Fire type zones must be set to Steady

39.2 Prewired 866 Class B Style W Modules using Single Notification Appliance

Prewired to XR2500F panel

DMP Model 866 45mA @ 12 VDC

The 866 Notification

Appliance Circuit

Module in alarm draws

up to 31mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input.

See the 866

Installation (LT-0059)

Normal/Silence Switch

1 AUX PWR

2 GND

3 Alarm In

4 Bell PWR In

5 Bell Out +

6 Bell Out -

7 Bell Trouble

8 Bell Trouble

Normal/Silence Switch

1 AUX PWR

2 GND

3 Alarm In

4 Bell PWR In

5 Bell Out +

6 Bell Out -

7 Bell Trouble

8 Bell Trouble

Model 310 1K EOL

Note: Terminals 3 and 4 jumper together to supply Bell Power from the panel

Model 310

1K EOL

Model 308

10K EOL

The maximum

voltage drop

between the panel Bell Output and the Model 308 EOL is 1 VDC when a separate power supply is not used.

Model 308

10K EOL

Listed, Polarized

Notification Appliance

Only one notification appliance may be used when not using a sync module.

See the Notification

The Bell Output programming for Fire type zones must be set to Temporal.

Appliance section for a

 

list of appliances.

Digital Monitoring Products

XR2500F Installation Guide

40

Page 48
Image 48
DMP Electronics XR2500F manual Wiring Diagrams, Prewired 866 Modules with NAC Extender