Compliance
Wiring Diagrams
39.1 Prewired 866 Modules with NAC Extender
Prewired to XR2500F panel
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
|
|
|
|
Model 310 |
| Model 310 | |
1K EOL |
|
| 1K EOL |
DMP Model 866 45mA @ 12 VDC
The 866 Notification
Appliance Circuit
Module in alarm draws
up to 31mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input.
See the 866
Installation
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Note: Terminals 3 and 4 jumper together to supply Bell Power from the panel
PowerPath NAC Extender
Models
PS-6E
See PowerPath installation for
detailed connection
instructions
The Bell Output programming for Fire type zones must be set to Steady
39.2 Prewired 866 Class B Style W Modules using Single Notification Appliance
Prewired to XR2500F panel
DMP Model 866 45mA @ 12 VDC
The 866 Notification
Appliance Circuit
Module in alarm draws
up to 31mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input.
See the 866
Installation
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Model 310 1K EOL
Note: Terminals 3 and 4 jumper together to supply Bell Power from the panel
Model 310
1K EOL
Model 308
10K EOL
The maximum
voltage drop
between the panel Bell Output and the Model 308 EOL is 1 VDC when a separate power supply is not used.
Model 308
10K EOL
Listed, Polarized
Notification Appliance
Only one notification appliance may be used when not using a sync module. | See the Notification |
The Bell Output programming for Fire type zones must be set to Temporal. | Appliance section for a |
| list of appliances. |
Digital Monitoring Products | XR2500F Installation Guide |