DIAGRAM 8 – Adding an 8840 Series Thermostat

MODEL 8870 THERMOSTAT

CAUTION!

TURN ALL DISTRIBUTION PANEL SWITCHES OFF BEFORE DOING ANY WIRING.

MODEL 8818 DISTRIBUTION PANEL

CAT-5

BRN

GRN

BLU/WHT

BLU

ORG/WHT

C

 

 

 

 

RC

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

RH

 

 

 

RSR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSC

 

R.V.

-Cool (O)

 

 

 

RSB

 

 

 

 

 

 

 

G

 

 

 

RSA

 

 

 

 

 

 

 

 

 

HUM W1

 

 

 

REF

 

 

 

 

 

 

 

 

 

DEH Y1

 

 

 

B-

 

 

 

 

 

 

 

 

 

W2

 

 

 

B+

 

 

 

 

 

 

 

 

 

Y2

 

 

 

 

 

 

 

 

 

 

 

 

A-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A+ A- B+

A

ON OFF

B

A

OFF ON

B

- B+ A- A+

ORG

ORG/WHT

BLU

ORG

A+ R.V.-Heat (B)

B- R C A+ A- B+ B- R C

ON OFF

PWR

A

ON OFF

B

ON OFF

PWR

24VAC

C R

OFF ON

PWR

FUSE

A

OFF ON

B

OFF ON

PWR

MAIN

PWR

ON OFF

C R B- B+ A- A+ C R B

BLU/WHT

GRN

BRN

ORG

ORG/WHT

BLU

BLU/WHT

BRN

GRN

CAT-5

MODEL 8809 COMMUNICATING SUB-BASE

 

MODEL 8848 SHOWN

 

 

 

 

 

Y2

Communication

 

CLK1

W1

Card

 

 

 

 

Y1

 

 

CLK2

 

 

 

 

 

RS2

G

 

 

 

 

YEL/BLU

RS1

R

 

24V

BLU

RS+v

ORG

1

24V(c)

ORG/WHT

 

 

 

 

 

W2

RED

 

2

ORG

 

 

 

 

 

BLK

 

 

 

40VA

TSTATWIRE2-

CABLE

40VA

XFRMR

 

WIRE TSTAT

CABLE

2-

 

BLU/WHT

BLU

RED

BLK

BRN

GRN

XFRMR

Model 8027 PLUG-IN TRANSFORMERS

IMPORTANT!

IMPORTANT!

YOU MUST ADDRESS 8840 SERIES

YOU MUST USE A SEPARATE POWER

THERMOSTATS HIGHER THAN ANY

SUPPLY FOR 8840 SERIES THERMOSTATS.

MODEL 8870 THERMOSTAT ON THE

 

 

 

NETWORK.

2.IMPORTANT! When addressing the thermostats, the Model 8870 thermostat(s) must either be the first addresses on the network, or there must be one address skipped between 8840 series thermostats. For example, if one Model 8870 thermostat were to be added to an existing four 8840 series thermostat network then the 8870 thermostat must be addressed #1 or #6. Change the existing address #1 to be #5 and add the 8870 as address #1, or simply add the new thermostat as address #6. IMPORTANT: Set “Number of Stats On Network” to 32 and Set BAUD Rate to 9600.

3.Unplug the Model 8811 Protocol Adapter power supply and RS-232 connection. Remove the four screws securing the cover to the base. Remove the pin jumpers (shunts) labeled JP9 (see ILLUSTRATION 13 for relative location). Replace the shunts on just one of the pins.

ILLUSTRATION 13 – Remove Terminating Resistors

PROTOCOL ADAPTER WITH

COVER REMOVED

 

 

 

 

JP9

Place these 2

 

 

 

 

 

 

 

 

 

 

jumpers on just

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

one pin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ11 Connectors

18