Emerson 30-130 kVA Battery Power Pack, 25-Inch Cabinet, Outline Drawing, 1/22/03

Models: 30-130 kVA

1 100
Download 100 pages 45.13 Kb
Page 43
Image 43
Outline Drawing,

BATTERY SERVICE ACCESS

CASTER CENTERS

12mm DIA. THREADED MOUNTING HOLE (4) TYP.

(SEE NOTES 12 & 13)

(SEE DETAIL A)

NOTES:

1.

ALL DIMENSIONS ARE IN INCHES.

2.

MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES

AT TOP FOR AIR EXHAUST.

3.

KEEP CABINET WITHIN 15° OF VERTICAL WHILE

HANDLING.

Figure 14

BIB

Battery Power Pack, 25-Inch Cabinet CONDUIT ENTRY 6.5 x 6.0

TOP ONLY

2 PLACES

MAX DOOR SWING 120°

1/22/032.72Manual backgroundManual background

12MM

 

CASTER

CENTERS

 

 

CENTERS

 

FRONT

 

 

12MM THREADED

 

MOUNTING HOLE

LEVELER

12MM CENTERS

DETAIL A

4.

EXTERIOR CABLE ENTRY AVAILABLE THROUGH

REMOVABLE TOP ACCESS PLATES. REMOVE, PUNCH

TO SUIT CONDUIT SIZE, AND REPLACE.

5.

CONTROL WIRING AND POWER WIRING MUST BE RUN

IN SEPARATE CONDUIT.

6.

ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE

NOT RECOMMENDED.

7.

ALL WIRING IS TO BE IN ACCORDANCE WITH

NATIONAL AND LOCAL ELECTRICAL CODES.

8.

RECOMMENDED OPERATING TEMPERATURE RANGE:

Outline Drawing,

BOARD

ACCESS

TOP VIEW

CENTER

GRAVITY

BOTTOM VIEW

CIRCUIT

BREAKER

CIRCUITMOTOR

BREAKER OPERATOR

OPTIONAL

DC BUS BARS

BATTERIES

NOTE:

(10)TRAY SHOWN.

(8)TRAY FOR FR200 BATTERY ASSY AND SMALLER

SUPPORT TRAY & SUPPORT BRACKET (SEE NOTE 15)

REAR OF UNIT SHOWN

WITHOUT SIDE PANEL

DC BUS BARS

CONTROL AND POWER WIRE SIDE ACCESS APPROX AREA 4.6 x 2.2

(BOTH SIDES)

CENTER

GRAVITY

68°F-77°F (20°C-25°C).

9. COLOR - IBM OFF WHITE.

10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR

FORKLIFT HANDLING.

11. APPROX WEIGHT OF CABINET IS 1500 TO 3000 LBS.

12. THREADED MOUNTING HOLES USED FOR SEISMIC

ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND

IS USED THE WEIGHT OF THE UNIT MUST BE

SUPPORTED UNDER ALL CASTERS.

13. EACH MOUNTING LOCATION IS SUPPORTED

BY (2) 10 GA. (.135") GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP.

MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM UNDERNEATH UNIT BASE.

14.REFER TO DETAIL A FOR DIMENSION TO FRAME WITH SIDE PANEL REMOVED. SIDE PANELS ARE REMOVED BETWEEN ADJACENT UNITS WHICH ARE BOLTED TOGETHER.

15."BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY" POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY AND TO THE CABINET. REFER TO THE APPROPRIATE USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS.

Battery Power Pack, 25-Inch Cabinet

Installation Drawings 33

FRONT VIEW

FRONT VIEW

 

 

 

WITH DOOR AND

 

SIDE VIEW

 

 

 

 

WITH DOOR

WITH COVER REMOVED

 

BARRIER REMOVED

DETAIL FOR DC BUS BARS

 

 

 

 

DRAWN BY

 

 

 

 

V CARMONA

OUTLINE DRAWING

 

 

 

CHK BY

DWG. NO.

 

 

25" BATTERY CABINET

 

 

 

 

UBC11001

 

 

NPOWER

 

 

REF. DWG.

REV. NO.

DATE

1050 DEARBORN DRIVE,

 

 

 

3

1/22/03

COLUMBUS, OHIO 43229

 

 

FILE NAME: Batts\UBC11001-03

 

Page 43
Image 43
Emerson 30-130 kVA installation manual Battery Power Pack, 25-Inch Cabinet, Outline Drawing, 1/22/03