CONTROL WIRING ILLUSTRATION

1

2

3

4

J2

 

 

 

5

 

 

 

 

 

 

 

6

 

 

 

 

7

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

2

 

 

 

 

3

 

IFM

 

 

4

J3

 

 

 

 

5

 

BOARD

6

 

UPS #2

7

 

 

 

 

8

 

 

 

 

 

 

 

 

 

1

2

3

4

56 TB57

7

8

9

10

IFM BOARD DETAIL

NOTES:

1.MODULE TO MODULE INTERCONNECTION CABLE ILLUSTRATED IS A STANDARD CATEGORY-5 ETHERNET PATCH CABLE. UPS SHIPS WITH A 25-FOOT CAT-5 PATCH CABLE FOR CUSTOMER USE. FOR APPLICATION REQUIRING LONGER CABLE LENGTH, A LONGER CAT-5 CABLE IS REQUIRED. PROVIDED BY OTHERS.

CONNECTION CAN BE MADE VIA THE CAT-5 PATCH CABLE AS SHOWN, OR BY TWISTED PAIR CONDUCTORS, SHOWN ON DWG# U37016. ONLY ONE CONTROL CABLE GROUP REQUIRED BETWEEN MODULES.

2.MAXIMUM CABLE LENGTH FOR CAT-5 PATCH CABLE IS 200 FEET.

3.BOTH UPS MODULES MUST BE CONFIGURED FOR 1+1 OPERATION. SEE OPTIONS MANUAL

FOR DETAILS.

4.CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM THE POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

5.REFER TO UPS MODULE CONNECTION LOCATION DIAGRAM FOR LOCATION OF IFM OPTION BOARD. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

6.ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES.

Figure 42 Control Wiring, 1+1 Category 5 Patch Cable Connection

Drawings 61

DRAWN BY

CONTROL WIRING

 

 

 

M MIERSEN

 

 

 

 

 

 

 

CHK BY

NPOWER 1+1 MODULE CONTROL CONNECTIONS

DWG. NO.

 

 

 

CAT-5 PATCH CABLE CONNECTION

 

U3713027

 

REF. DWG.

NPOWER

REV. NO.

DATE

1050 DEARBORN DRIVE

 

 

6/17/03

COLUMBUS, OHIO 43229

 

 

 

 

 

FILE NAME: Npower\Drawings\Options1+1\U3713027\(D)

 