Site Planning Data

 

 

 

 

 

 

 

220 OR 240 VAC INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

 

Standard AC Input

AC Input with Filter

AC Output

 

 

 

 

 

 

Concen-

 

Rating

AC Voltage

without Filter

 

Option

 

Current

 

Max.

Max. Heat

 

Approx.

 

trated

 

 

 

 

 

 

 

Recom-

 

 

 

Recom-

 

 

 

Battery

Dissipation

Dimensions

Unpacked

 

Floor

Cooling

 

 

 

 

 

 

mended

 

 

 

mended

 

Rec.

Battery

Disch.

BTU/hr

WxDxH

Weight

 

Loading

 

 

 

 

 

 

 

 

 

 

 

Air

kVA

kW

Input

Output

Nom

Max

OPCD

Nom

Max

 

OCPD

Nom

OCPD

KW

(Amps)

Full Load

(Inches)

(Pounds)

 

(Lb/SqFt)

(CFM)

30

24

220

208

87

108

150

75

94

 

125

83

125

26

66A

8,500

31.7x32.5x71

2,200

 

307

720

30

24

220

220

87

108

150

75

94

 

125

79

100

26

66A

8,500

31.7x32.5x71

2,200

 

307

720

30

24

240

208

79

99

125

69

86

 

125

83

125

26

66A

8,500

31.7x32.5x71

2,200

 

307

720

30

24

240

240

79

99

125

69

86

 

125

72

100

26

66A

8,500

31.7x32.5x71

2,200

 

307

720

40

32

220

208

115

144

175

100

125

 

150

111

150

34

88A

11,000

31.7x32.5x71

2,200

 

307

720

40

32

220

220

115

144

175

100

125

 

150

105

150

34

88A

11,000

31.7x32.5x71

2,200

 

307

720

40

32

240

208

106

132

175

92

115

 

150

111

150

34

88A

11,000

31.7x32.5x71

2,200

 

307

720

40

32

240

240

106

132

175

92

115

 

150

96

125

34

88A

11,000

31.7x32.5x71

2,200

 

307

720

50

40

220

208

144

180

225

125

157

 

200

139

175

43

109A

14,000

31.7x32.5x71

2,200

 

307

720

50

40

220

220

144

180

225

125

157

 

200

131

175

43

109A

14,000

31.7x32.5x71

2,200

 

307

720

50

40

240

208

132

165

200

115

144

 

175

139

175

43

109A

14,000

31.7x32.5x71

2,200

 

307

960

50

40

240

240

132

165

200

115

144

 

175

120

150

43

109A

14,000

31.7x32.5x71

2,200

 

307

960

65

52

220

208

183

229

300

161

202

 

250

180

225

55

141A

18,000

39.4x32.5x71

2,700

 

304

960

65

52

220

220

183

229

300

161

202

 

250

171

225

55

141A

18,000

39.4x32.5x71

2,700

 

304

960

65

52

240

208

168

210

250

148

185

 

225

180

225

55

141A

18,000

39.4x32.5x71

2,700

 

304

960

65

52

240

240

168

210

250

148

185

 

225

156

200

55

141A

18,000

39.4x32.5x71

2,700

 

304

960

80

64

220

208

225

281

350

198

248

 

300

222

300

68

174A

22,000

39.4x32.5x71

2,700

 

304

960

80

64

220

220

225

281

350

198

248

 

300

210

300

68

174A

22,000

39.4x32.5x71

2,700

 

304

960

80

64

240

208

206

258

350

182

227

 

300

222

300

68

174A

22,000

39.4x32.5x71

2,700

 

304

960

80

64

240

240

206

258

350

182

227

 

300

192

250

68

174A

22,000

39.4x32.5x71

2,700

 

304

960

100

80

220

208

280

350

450

247

308

 

400

278

350

85

218A

26,000

49.2x32.5x71

3,800

 

342

1440

100

80

220

220

280

350

450

247

308

 

400

262

350

85

218A

26,000

49.2x32.5x71

3,800

 

342

1440

100

80

240

208

256

321

400

226

283

 

350

278

350

85

218A

26,000

49.2x32.5x71

3,800

 

342

1440

100

80

240

240

256

321

400

226

283

 

350

241

300

85

218A

26,000

49.2x32.5x71

3,800

 

342

1440

130

104

220

208

364

455

600

321

401

 

500

361

450

111

283A

22,000

49.2x32.5x71

3,800

 

342

1440

130

104

220

220

364

455

600

321

401

 

500

341

450

111

283A

22,000

49.2x32.5x71

3,800

 

342

1440

130

104

240

208

333

417

500

294

368

 

450

361

450

111

283A

22,000

49.2x32.5x71

3,800

 

342

1440

130

104

240

240

333

417

500

294

368

 

450

313

400

111

283A

22,000

49.2x32.5x71

3,800

 

342

1440

Notes:

 

 

 

1,3,4,5,7,8, 9,11,12, 13

 

 

 

2,3,5,7,8,9,11,12

6,8,9,11,12

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

87

Page 97
Image 97