34 Installation Drawings

34 Installation Drawings

AIR EXHAUST CUTOUT

6 PLACES

CASTER CENTERS

12MM

CENTERS

CONDUIT ENTRY

5.5 X 11.0FRONT TOP AND BOTTOM

DC BUS BARS

12mm DIA. THREADED MOUNTING HOLE (6) TYP. (SEE NOTES 12 & 13)

(SEE DETAIL A)

CASTER

CENTERS

2.72Figure 15 Outline Drawing,

NOTES:

1.ALL DIMENSIONS ARE IN INCHES.

2.MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES AT TOP FOR AIR EXHAUST.

3.KEEP CABINET WITHIN 15° OF VERTICAL WHILE HANDLING.

4.EXTERIOR CABLE ENTRY AVAILABLE THROUGH REMOVABLE TOP AND BOTTOM ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE, AND REPLACE.

5.CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUIT.

6.ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.

7.ALL WIRING IS TO BE IN ACCORDANCE WITH

Figure 15 Outline Drawing,

MAX DOOR SWING 120°- LIFT OFF DOORS

12MM CENTERS

 

TOP VIEW

BOTTOM VIEW

12MM THREADED

 

MOUNTING HOLE

LEVELER

NATIONAL AND LOCAL ELECTRICAL CODES.

8.

RECOMMENDED OPERATING TEMPERATURE RANGE:

68°F-77°F (20°C-25°C).

9.

COLOR - IBM OFF WHITE.

10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR

FORKLIFT HANDLING.

Battery Power

CIRCUIT

DETAIL A

REAR OF UNIT SHOWN

11. APPROX WEIGHT OF CABINET IS 3500 TO 5100 LBS.

BREAKER

BATTERIES

WITHOUT SIDE PANEL

MOTOR

OPERATOR

OPTIONAL

12. THREADED MOUNTING HOLES USED FOR SEISMIC

ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND

IS USED THE WEIGHT OF THE UNIT MUST BE

SUPPORTED UNDER ALL CASTERS.

13. EACH MOUNTING LOCATION IS SUPPORTED

BY (2) 10 GA. (.135") GALVANIZED STEEL. THE

THREADED 12MM INSERT IS APPROX. 3/4" DEEP.

CIRCUIT

CONTROL AND

BREAKER

POWER WIRE

 

SIDE ACCESS

BUS BARS

APPROX AREA

4.56 x 2.25

 

 

(BOTH SIDES)

CENTER

CENTER

GRAVITY

GRAVITY

SUPPORT TRAY &

 

SUPPORT BRACKET

 

(SEE NOTE 15)

 

MOUNTING BOLTS MUST BE THREADED INTO UNIT

MOUNTING HOLES FROM UNDERNEATH UNIT BASE.

14.REFER TO DETAIL A FOR DIMENSION TO FRAME WITH SIDE PANEL REMOVED. SIDE PANELS ARE REMOVED BETWEEN ADJACENT UNITS WHICH ARE BOLTED TOGETHER.

15."BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY" POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY AND TO THE CABINET. REFER TO THE APPROPRIATE LIEBERT USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS.

 

FRONT VIEW

 

SIDE VIEW

 

FRONT VIEW

WITH DOORS REMOVED

 

DETAIL FOR DC BUS BARS

WITH COVER REMOVED

 

 

 

DRAWN BY

 

 

 

 

V CARMONA

OUTLINE DRAWING

 

 

 

CHK BY

DWG. NO.

 

 

49" BATTERY CABINET

 

 

 

 

UBC11003

 

 

NPOWER

 

 

REF. DWG.

REV. NO.

DATE

1050 DEARBORN DRIVE,

 

 

3

1/22/03

COLUMBUS, OHIO 43229

 

 

FILE NAME: Batts\UBC11003-03

 

Pack, 49-Inch Cabinet