FRONT VIEW WITH DOOR CLOSED

FRONT VIEW WITH DOOR OPEN

AND ACCENT REMOVED

RIGHT SIDE VIEW

PANELBOARD ENDWALL

ONE-LINE DIAGRAM

NOTES:

1.SIZE "A" SYSTEM PARALLELING PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA.

2.ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRIC CODES.

3.PANELBOARD EXTERIOR IS CODE GAUGE GALVANIZED STEEL. BOTH ENDWALLS ARE BLANK. ANSI 49 GRAY BAKED ENAMEL FINISH. LOCK IS FLUSH MOUNTED.

4.NEMA-1 PANELBOARD CONSTRUCTED FOR WALL-MOUNTING ONLY.

5.FRONT ACCESS ONLY REQUIRED PER NEC ARTICLE 110-16. TOP OR BOTTOM CABLE ENTRY/EXIT.

6.COPPER BUSSING IS STANDARD.

Figure 26 Outline Drawing, 1+1 Paralleling Panelboard, Configuration “N,”

Installation

ONE-LINE LEGEND

7. OVERCURRENT PROTECTIVE DEVICES ARE AUTOMATIC MOLDED CASE CIRCUIT BREAKERS.

8. LUG SIZE RANGES ARE BASED ON COPPER CONDUCTORS. ALUMINUM AND COPPER-CLAD ALUMINUM CONDUCTORS ARE NOT RECOMMENDED.

9. REFERENCE COMMON INFORMATION DRAWING #U3711007

FOR ADDITIONAL PANELBOARD DETAILS.

Size “A”

Drawings 45

DRAWN BY

OUTLINE DRAWING

 

 

 

M MIERSEN

 

 

 

NPOWER 1+1

 

 

 

CHK BY

DWG. NO.

 

 

SYSTEM PARALLELING PANELBOARD

 

 

 

 

U3711008

 

REF. DWG.

CONFIGURATION "N", SIZE "A"

REV. NO.

DATE

1050 DEARBORN DRIVE,

 

 

 

6/17/03

COLUMBUS, OHIO 43229

FILE NAME: I/APPL/NPOWER/DRAWINGS/OUTLINES/1+1SPC/U3711008/(C)

Page 55
Image 55
Emerson 30-130 kVA installation manual Outline Drawing, 1+1 Paralleling Panelboard, Configuration N