10.0WIRING INSPECTION

￿￿9HULI\￿DOO￿SRZHU￿FRQQHFWLRQV￿DUH￿WLJKW￿

￿￿9HULI\￿DOO￿FRQWURO￿ZLUH￿WHUPLQDWLRQV￿DUH￿WLJKW￿

￿￿9HULI\￿DOO￿SRZHU￿ZLUHV￿DQG￿FRQQHFWLRQV￿KDYH￿SURSHU￿VSDFLQJ￿EHWZHHQ￿H[SRVHG￿VXUIDFHV￿￿SKDVH￿WR￿ SKDVH￿DQG￿SKDVH￿WR￿JURXQG￿￿

￿￿9HULI\￿WKDW￿DOO￿FRQWURO￿ZLUHV￿DUH￿UXQ￿LQ￿LQGLYLGXDO￿￿VHSDUDWH￿￿VWHHO￿FRQGXLW￿

Table 1 Power Wiring Terminals - Factory Supplied

UPS Module Rating

Connection Type

30-130 kVA

Bus bars. See Outline Drawings for dimensions.

 

 

Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16(see Table 3 of this manual) and associated notes of the National Electrical Code (NFPA 70).

Use commercially available solderless lugs for the wire size required for your application. Connect wire to the lug using tools and procedures specified by the lug manufacturer.

Table 2

Torque Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nut and Bolt Combinations

 

 

 

 

 

 

 

 

 

 

Grade 2

 

Electrical Connections

 

 

 

Standard

 

with Belleville Washers

 

 

 

 

 

 

 

 

 

 

Bolt Shaft Size

 

Lb-in

 

 

N-m

Lb-in

N-m

 

1/4

 

53

 

 

6.0

46

5.2

 

 

 

 

 

 

 

 

 

 

5/16

 

107

 

 

12

60

6.8

 

 

 

 

 

 

 

 

 

 

3/8

 

192

 

 

22

95

11

 

 

 

 

 

 

 

 

 

 

1/2

 

428

 

 

48

256

29

 

 

 

 

 

Circuit Breakers With Compression Lugs (For Power Wiring)

 

 

Cable Size or Range

 

Lb-in

 

 

N-m

 

 

 

#6 - #4

 

100

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

#3 - #1

 

125

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

1/0 - 2/0

 

150

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

3/0 - 200 MCM

 

200

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

250 - 400 MCM

 

250

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

500 - 700 MCM

 

300

 

 

34

 

 

 

 

 

 

 

 

Terminal Block Compression Lugs (For Control Wiring)

 

 

 

AWG Wire Size or Range

 

Lb-in

 

 

N-m

 

 

 

#22 - #14

 

3.5 to 5.3

 

0.4 to 0.6

 

 

 

 

 

 

 

 

 

 

 

Use the values in this table unless the equipment is labeled with a different torque value.

￿

28 Wiring Inspection

Page 38
Image 38