Lincoln Electric SVM123-A service manual Connecting the NA-5 to the Idealarc DC-1000

Models: SVM123-A

1 113
Download 113 pages 14.33 Kb
Page 27
Image 27

C-3

ACCESSORIES

C-3

 

 

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

d.Tape the #21 lead to work cable for ease of use.

6.Connect the welding cables as shown in Figure C.1.

NOTE: Welding cables must be of proper capacity for the current and duty cycle for immediate and future applications.

NOTE: The connection diagram shown in Figure C.1 shows the electrode connected for positive polarity. To change polarity:

a.Set the IDEALARC DC-1000 ON/OFF PUSH BUTTON to OFF.

b.Move the electrode cable to the Negative (-) output terminal.

c.Move the work cable to the Positive (+) output terminal.

d.Set the IDEALARC DC-1000 CONTROL CIRCUIT POLARITY SWITCH to NEGA- TIVE.

e.Reverse the leads at the back of the ammeter and voltmeter on the wire feeder automatic control box.

CONNECTING THE NA-5 TO THE IDEALARC DC-1000

NOTE: For optimum performance, use the NA-5 with IDEALARC DC-1000 codes 8288 and above.

1.Disconnect main AC input power to the IDE- ALARC DC-1000.

2.Set the IDEALARC DC-1000 ON/OFF PUSH BUTTON to OFF.

3.Connect the wire feeder control cable leads to the IDEALARC DC-1000 terminal strip as shown in Figure C.2.

NOTE: If using a K215 control cable, connect con- trol cable leads #75 to #75 on the terminal strip, #76 to #74 on the terminal strip, and #77 to #73 on the terminal strip.

4.Connect the wire feeder control cable ground lead

to the frame terminal marked .

CAUTION

The IDEALARC DC-1000 must be properly grounded.

____________________________________________________

5.Extend wire feeder control cable lead #21 so it can be connected directly to the work piece.

a.Make a bolted connection using AWG #14 or larger insulated wire.

b.Tape the bolted connection with insulating tape.

NOTE: An S-16586-X remote voltage sensing work lead is available for this purpose.

c.Keep the #21 lead electrically separate from the work cable circuit and connection.

d.Tape the #21 lead to work cable for ease of use.

6.Connect NA-5 wire feeder control jumpers on the Voltage Control Board. See NA-5 Operator’s Manual.

a.Connect red jumper on Voltage Control Board to pin “S.”

b.Connect white jumper on Voltage Control Board to pin “B.”

7.Connect the welding cables as shown in Figure C.2.

NOTE: Welding cables must be of proper capacity for the current and duty cycle for immediate and future applications.

FIGURE C.2 - NA-5 Wire Feeder Connection to

the IDEALARC DC-1000

IDEALARC DC-1000

Page 27
Image 27
Lincoln Electric SVM123-A service manual Connecting the NA-5 to the Idealarc DC-1000