Lincoln Electric SVM123-A service manual Figure F.4 Main Secondary Lead Test Points

Models: SVM123-A

1 113
Download 113 pages 14.33 Kb
Page 58
Image 58

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

F-18

TROUBLESHOOTING & REPAIR

F-18

 

 

MAIN TRANSFORMER (T1) VOLTAGE TEST

FIGURE F.4 - Main Secondary Lead Test Points

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

a.If one or more of the above voltage tests are incorrect, check for loose or faulty wiring. If the wiring is good, then the Main Transformer may be faulty.

NOTE: A long wire with clip or a long probe may be required to reach the lower middle lead.

7.Test for 115 VAC between leads #31 to #32 on the terminal strip. These can be accessed through the front panel assembly door.

a.If the 115 VAC is not pre- sent, check for loose or faulty wiring or blown fuse. If necessary, untape and track the continuity of leads #31 and #32 through the entire harness.

b.If the wiring is good, then the Main Transformer may be faulty.

8.Remove the screws from the control box cover. It does not have to be completely removed to perform this test.

9.Test with an AC voltmeter for 75 VAC for each phase angle winding as shown. See Figure F.5.

NOTE: If the main supply voltage varies, the Main Transformer volt- ages will vary proportionately. See Figure F.5.

IDEALARC DC-1000

Page 58
Image 58
Lincoln Electric SVM123-A service manual Figure F.4 Main Secondary Lead Test Points