E-14

 

TROUBLESHOOTING

E-14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Observe all Safety Guidelines detailed throughout this manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE DRIVE MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error Code #

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

81

Motor Overload

 

 

Long term average motor current limit has been exceeded. Typically

 

 

 

 

 

 

 

indicates mechanical overload of system. If problem continues consider

 

 

 

 

 

 

 

higher gear ratio.

 

 

 

 

 

 

 

 

 

 

 

 

82

Motor Overcurrent

 

 

Absolute maximum motor current level has been exceeded. This is a

 

 

 

 

 

 

 

short term average to protect drive circuitry.

 

 

 

 

 

 

 

 

 

 

 

 

 

83

Shutdown #1

 

 

The normally closed circuit of Shutdown #1 has been interrupted.

 

 

 

 

 

 

 

 

 

Check the connection between pins 9 and 10 on the External I/O con-

 

 

 

 

 

 

 

nector (S7).

 

 

 

 

 

 

 

 

 

 

 

 

 

84

Shutdown #2

 

 

The normally closed circuit of Shutdown #2 has been interrupted.

 

 

 

 

 

 

 

 

 

Check the connection between pins 9 and 11 on the External I/O con-

 

 

 

 

 

 

 

nector (S7).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMMUNICATION MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error Code #

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

118

DeviceNet connection error

 

 

Lost Connection with DeviceNet Master

 

 

 

 

 

 

 

 

 

 

 

 

 

119

DeviceNet de-allocation error

 

 

The DeviceNet Master de-allocated the connection

 

 

 

 

 

 

 

 

 

 

 

 

 

133

Write ArcLink action failure

 

 

May be caused by activating Cold Inch while welding through

 

 

 

 

 

 

 

 

 

DeviceNet

 

 

 

 

 

 

 

 

 

 

 

 

145

Duplicate MAC ID error

 

 

Check MAC ID assignments on DeviceNet Setup Dip switch Bank (S2)

 

 

 

 

 

 

 

 

 

 

 

146

DeviceNet Bus off

 

 

Check condition of on board DeviceNet Status indicators

 

 

 

 

 

 

 

 

 

 

 

 

 

147

DeviceNet polled I/O error

 

 

Problem changing attribute over polled I/O

 

 

 

 

 

 

 

 

 

 

 

 

 

149

DeviceNet I/O data error

 

 

Received DeviceNet I/O data with wrong number of bytes

 

 

 

 

 

 

 

 

 

 

 

 

 

169

Ethernet Connection Time out

 

 

Loss of communication with PC Application.

 

 

 

 

171

Ethernet Socket Time out

 

 

 

 

 

 

 

172

Ethernet Watch Dog Time out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

194

Ethernet Send Problem

 

 

Communication problem between Master and Slave machines.

 

 

 

 

195

Ethernet Problem

 

 

 

 

 

 

 

197

Ethernet Problem

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

198

Ethernet Client Time out

 

 

Master lost communications with Slave Machine.

 

 

 

 

 

 

 

 

 

 

 

 

 

216

Ethernet Problem

 

 

Communication problem between Master and Slave machines.

 

 

 

 

 

 

 

 

 

 

 

 

 

224

Ethernet Problem

 

 

Master had problem connecting to a Slave machine.

 

 

 

 

 

 

 

 

 

 

 

 

 

226

Ethernet Problem

 

 

Communication problem between Master and Slave machines.

 

 

 

 

 

 

 

 

 

 

 

 

 