A-24

INSTALLATION

A-24

 

 

 

DEVICENET CONFIGURATION

For systems controlled via DeviceNet, The MAC ID and baud rate must be properly configured (see the Internal Controls section of this document). Other information regarding basic system integration of the Power Wave AC/DC 1000 with a DeviceNet PLC is provided in the DeviceNet Interface Specification (part of the Power Wave Submerged Arc Utilities software package available on CD from the Lincoln Electric

Company).

INTERNAL CONTROLS

INTERNAL CONTROLS DESCRIPTION

(See figure A.4)

The P.C. Boards located behind the Power Wave AC/DC 1000 front access panel are equipped with DIP switches for custom configuration. To access the DIP switches:

WARNING

ELECTRIC SHOCK can kill.

Do not touch electrically live parts or electrodes with your skin or wet clothing.

Insulate yourself from the work and ground.

Always wear dry insulating gloves.

-----------------------------------------------------------

1.Turn off power at the disconnect switch.

2.Remove the screws securing the front access panel.

3.Open the access panel, allowing the weight of the panel to be carried by the hinge tab at the bottom. Make sure the weight of the access panel is sup- ported by the hinge tabs, not the wiring harness.

4.Adjust the DIP switches as necessary (see infor- mation below).

5.Replace the panel and screws, and restore power.

FIGURE A.4

CONTROL

P.C. BOARD

S1

S2

S1

S1

S4S3

ETHERNET

P.C. BOARDFEEDHEAD P.C. BOARD

POWER WAVE® AC/DC 1000

Page 34
Image 34
Lincoln Electric 11226, 11124 manual Devicenet Configuration, Internal Controls Description