E-7

 

 

TROUBLESHOOTING

 

E-7

 

 

 

 

 

 

 

Observe all Safety Guidelines detailed throughout this manual

 

 

 

 

 

 

 

PROBLEMS

 

POSSIBLE

 

RECOMMENDED

 

(SYMPTOMS)

 

CAUSE

 

COURSE OF ACTION

 

 

 

 

 

 

 

 

DEVICENET-PLC CONTROLLED SYSTEM

 

 

 

 

 

 

 

 

 

4. Power Supply.

 

4. Verify that the DeviceNet bus power

 

 

 

 

 

supply can supply sufficient current

 

 

 

 

 

for the devices on the network.

 

 

 

5. Expected Packet Rate.

 

5. Verify that 1000/(Expected Packet

 

 

 

 

 

Rate) ￿ (scans per second). The

 

 

 

 

 

DeviceNet tab of the Diagnostics

 

 

 

 

 

Utility displays these values.

 

 

 

 

 

Output will not come on.

 

1. DeviceNet trigger not asserted.

 

1. From the DeviceNet tab of the

 

 

 

 

 

Diagnostics Utility, select Monitor.

 

 

 

 

 

The Monitor window will be dis-

 

 

 

 

 

played. Verify under the "Produced

 

 

 

 

 

Assembly" that "Trigger" is highlight-

 

 

 

 

 

ed.

 

 

 

2. Touch Sense command.

 

2. From the DeviceNet tab of the

 

 

 

 

 

Diagnostics Utility, select Monitor.

 

 

 

 

 

The Monitor window will be dis-

 

 

 

 

 

played. Verify under the "Produced

 

 

 

 

 

Assembly" that "Touch Sense" is

 

 

 

 

 

NOT highlighted.

 

 

 

3. Passive Mode.

 

3. The DeviceNet tab of the

 

 

 

 

 

Diagnostics Utility displays the

 

 

 

 

 

Power Wave’s passive mode status.

 

 

 

 

 

If the status needs to be changed,

 

 

 

 

 

select Configure, and make the nec-

 

 

 

 

 

essary modification.

 

 

 

4. Welding Cables.

 

4. Verify that welding cables are con-

 

 

 

 

 

nected properly.

 

 

 

5. Output Disabled.

 

5. From the DeviceNet tab of the

 

 

 

 

 

Diagnostics Utility, select Monitor.

 

 

 

 

 

The Monitor window will be dis-

 

 

 

 

 

played. Verify under the "Produced

 

 

 

 

 

Assembly" that "Disable Output" is

 

 

 

 

 

NOT highlighted.

 

 

 

6. Other modules faulted.

 

6. Verify no other modules are faulted

 

 

 

 

 

(all system Status Lights should be

 

 

 

 

 

steady green). Use Diagnostics

 

 

 

 

 

Utility to display any current faults in

 

 

 

 

 

the system.

 

 

 

 

 

 

CAUTION

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.