Nameplate

Catalog Number Identification

The Transfer Switch nameplate includes data for each specific ASCO Series 300 ATS. Use the ATS only within the limits shown on this nameplate.

A typical Catalog Number is shown below with its elements explained. The example is for a G–design Series 300 ATS with switched neutral, 3 pole, 2000 amp, 480 V, in a Type 1 enclosure:

G3003 2000 N 1 C

Neutral

 

Phase Poles

B – switched

 

2

– single Ø

C – overlapping

 

3

– three Ø

blank – solid

 

 

 

 

 

 

 

Amperes

1000

1200

1600

2000

2600

3000

Voltage

C 208

L 440

D 220

M 460

E 230

N 480

F 240

P 550

H 380

Q 575

J 400

R 600

Controller

1 – standard

1X – if accessories ordered

Enclosure

C – type 1 F – type 3R G – type 4 * L – type 12 *

blank – open type

K 415

*type 4 & 12 enclosures are available only for 1000, 1200, & 1600 amp. sizes

neutral connections

power connections

Transfer

Switch

power connections

neutral connections

terminal block TB for

engine start and switch

position contacts

Controller

membrane controls

2000 amp. size in typical enclosure with location of customer connections