CONTROL FEATURES (continued)

INPHASE MONITOR

FOR MOTOR LOAD TRANSFER

Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.

The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.

FUNCTION

S1 DIP SWITCH

 

 

 

enable

Actuator 5 on

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disable

Actuator 5 off

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

Note

If the Motor Load Transfer feature is enabled, it will be activated following the Load Disconnect Feature Delay Before Transfer delay.

LOAD DISCONNECT FEATURE

Connect external circuits to the terminals indicated on the Wiring Diagram provided with the ATS.

The double throw (Form C) contact is rated for

28 VDC or 120 VAC (5 amperes resistive). The contact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the Automatic Transfer Switch. The contact resets either immediately following transfer or after the same delay as set for pre–signal before transfer.

Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:

Delay Before Transfer

LD TDBT

S2 DIP SWITCH

 

 

 

 

 

Actuator 7 on

 

 

 

 

 

 

 

 

 

 

0 (disable)

 

 

 

 

 

 

7

 

Actuator 8 on

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 seconds

Actuator 7 on

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

Actuator 8 off

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 seconds

Actuator 7 off

 

 

 

 

 

7

 

 

 

 

 

 

 

 

Actuator 8 on

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 seconds

Actuator 7 off

 

 

 

7

 

 

 

 

 

 

 

 

Actuator 8 off

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

 

Delay After Transfer*

 

 

S2 DIP SWITCH

LD TDAT

 

 

 

 

enable

 

Actuator 6 on

 

 

 

 

 

6

disable

Actuator 6 off

6

*Enabling the Delay After Transfer will cause the control signal to reset after the same delay as set for the Delay Before Transfer.

REMOTE CONTROL FEATURES

These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.

Remote Test (terminals CP6–7)

RTSW

S2 DIP SWITCH

 

 

 

disable

Actuator 3 on

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 3 off

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Transfer to Emergency (CP8–9)

RT /E

S2 DIP SWITCH

 

 

 

disable

Actuator 2 on

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 2 off

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass Transfer Time Delay (CP12–13)

TD E/N BYP.

S2 DIP SWITCH

 

 

 

disable

Actuator 1 on

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 1 off

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inhibit Transfer to Emergency (CP10–11)

N/E INHIB.

S2 DIP SWITCH

 

 

 

disable

Actuator 4 on

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 4 off

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5---4