Controls and Indicators

7.0CONTROLS AND INDICATORS

Battery Level Indicators

 

Load Level Indicators

Fault Indicator

Bypass Indicator

AC Input Indicator

Inverter Indicator

On/Alarm Silence/Manual

Liebert® GXT3

Battery Test Button

AC Power System

10000VA

Standby/Manual Bypass Button

Battery Indicator

7.1ON/Alarm Silence/Manual Battery Test Button

This button controls output power to connected load(s) and has three functions:

ON

Alarm Silence

Manual Battery Test

ON - Pressing this button for four seconds will start the UPS.

Alarm Silence - To silence alarms, press this button for at least one second. After the alarm is silenced, the Liebert GXT3 will reactivate the alarm system to alert of additional problems.

NOTE

The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.

Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from mains power with no alarm conditions present.

If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24 hours.

After 24 hours, retest the batteries.

After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer, Emerson® representative or Emerson Channel Support.

7.2Standby/Manual Bypass Button

This button controls output power to connected load(s) and has dual functions:

Standby and Manual Bypass.

NOTICE

Pressing the Standby/Manual Bypass button once will transfer the load to bypass power and the load will be unprotected from disturbances in utility supply. Pressing the Standby/Manual Bypass button twice within 4 seconds while on Bypass will cut