Specifications

Table 11 Battery run time, minutes, all models

Number of

Load Percent

230VAC RT Models

 

 

 

Batteries/Cabinets

of Capacity

5kVA

6kVA

10kVA

 

10%

460

360

316

 

 

 

 

 

 

20%

205

191

163

 

 

 

 

 

 

30%

159

138

137

 

 

 

 

 

 

40%

124

108

107

Internal Battery

 

 

 

 

50%

106

97

82

+ 4 External

 

 

 

 

60%

98

81

69

Battery Cabinets

 

70%

83

71

52

 

 

 

 

 

 

80%

75

61

48

 

 

 

 

 

 

90%

66

51

44

 

 

 

 

 

 

100%

53

48

40

 

 

 

 

 

Using the configuration program, the user may specify the number of GXT3-240VBATT external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 11 shows the estimated run times at different loads.

12.1Auto-Learning Battery Run Times

As batteries age, the estimated run times may become less accurate. The Liebert GXT3 is programmed to “learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.

The UPS will update the anticipated run time calculation only under certain conditions.

The UPS must have a steady load that is greater than 20%.

The UPS must be at 100% charge at the start of a battery discharge.

The battery discharge must continue uninterrupted until the batteries reach their end-of- discharge voltage.

If all conditions are not met, the run time calculation will not be modified.

If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is Auto-Learned.