Installation and Configuration

Figure 12 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS

PD2-CE6HDWRMBS

PD2-CE10HDWRMBS

L N

L N

OUTPUT

INPUT

NOTE

L N

L N

INPUT

OUTPUT

The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.

The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.

Liebert® GXT3

18

Page 24
Image 24
Emerson 5000-10, 000-VA, 230V user manual Output Input