Specifications

Table 11 Battery run time, minutes, all models

Number of

Load Percent

230VAC RT Models

 

 

 

Batteries/Cabinets

of Capacity

5kVA

6kVA

10kVA

 

10%

105

97

81

 

 

 

 

 

 

20%

52

47

39

 

 

 

 

 

 

30%

40

33

22

 

 

 

 

 

 

40%

27

22

15

 

 

 

 

 

Internal Battery

50%

21

17

11

 

 

 

 

60%

17

14

9

 

 

 

 

 

 

 

70%

14

11

7

 

 

 

 

 

 

80%

12

9

5

 

 

 

 

 

 

90%

10

8

4

 

 

 

 

 

 

100%

9

6

3

 

 

 

 

 

 

10%

187

158

149

 

 

 

 

 

 

20%

106

97

82

 

 

 

 

 

 

30%

78

65

50

 

 

 

 

 

 

40%

53

48

39

Internal Battery

 

 

 

 

50%

47

40

28

+ 1 External

 

 

 

 

60%

40

33

22

Battery Cabinet

 

70%

34

26

17

 

 

 

 

 

 

80%

28

22

15

 

 

 

 

 

 

90%

23

19

13

 

 

 

 

 

 

100%

21

17

11

 

 

 

 

 

 

10%

217

205

191

 

 

 

 

 

 

20%

146

123

128

 

 

 

 

 

 

30%

106

97

82

 

 

 

 

 

 

40%

91

74

60

Internal Battery

 

 

 

 

50%

71

53

47

+ 2 External

 

 

 

 

60%

53

48

39

Battery Cabinets

 

70%

49

43

32

 

 

 

 

 

 

80%

45

38

26

 

 

 

 

 

 

90%

41

33

22

 

 

 

 

 

 

100%

37

28

18

 

 

 

 

 

 

10%

360

223

224

 

 

 

 

 

 

20%

188

158

150

 

 

 

 

 

 

30%

132

110

112

 

 

 

 

 

 

40%

106

97

82

Internal Battery

 

 

 

 

50%

95

78

66

+ 3 External

 

 

 

 

60%

79

66

50

Battery Cabinets

 

70%

68

52

45

 

 

 

 

 

 

80%

53

48

40

 

 

 

 

 

 

90%

50

44

34

 

 

 

 

 

 

100%

47

41

28

 

 

 

 

 

Liebert® GXT3

38

Page 44
Image 44
Emerson 230V, 5000-10, 000-VA user manual Battery run time, minutes, all models