Specifications

12.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

 

 

 

 

 

Model #

GXT3-5000RT230

 

GXT3-6000RT230

GXT3-10000RT230

Rating

 

5000VA/4000W

 

6000VA/4800W

10000VA/9000W

Dimensions, mm (in)

 

 

 

 

 

Unit, W x D x H

430 x 574 x 217 (16.9 x 22.4 x 8.5)

430 x 581 x 261 (16.9 x 22.9 x 10.3)

 

 

 

 

 

Shipping, W x D x H

516 x 745 x 530 (20.3 x 29.3 x 20.9)

530 x 745 x 563 (20.9 x 29.3 x 22.2)

 

 

 

 

 

Weight, kg (lb)

 

 

 

 

 

Unit

60 (132.2)

70 (154.3)

 

Shipping

71 (156.5)

92 (202.8)

 

 

 

 

 

Input AC Parameters

 

 

 

 

Operating Frequency, Nom

 

 

50 or 60Hz (Factory Default = 50)

 

Factory Default VAC

 

 

230VAC

 

 

 

 

 

 

 

User-Configurable VAC

 

 

220/230/240VAC

 

(May be modified using included configuration program)

 

 

Operating Voltage Range

 

 

176 - 280VAC

 

Without Battery Operation

 

 

 

 

 

 

 

Maximum Allowable VAC

 

 

280VAC

 

Input Frequency Without

 

 

40 - 70Hz

 

 

Battery Operation

 

 

 

 

 

 

 

 

 

 

PD2-CE6HDWRMBS Standard

PD2-CE10HDWRMBS Standard

Input Power Connection

(See 3.3 - Removable Power

(See 3.3 - Removable Power Distribution Box)

 

 

Distribution Box)

 

 

 

 

 

Output AC Parameters

 

 

 

 

 

AC-AC Efficiency

 

 

92% AC-AC

 

 

Factory Default VAC

 

 

230VAC

 

 

 

 

 

 

 

 

 

PD2-CE6HDWRMBS Standard

PD2-CE10HDWRMBS Standard

 

Output Connections

(See 3.3 - Removable Power

 

(See 3.3 - Removable Power Distribution Box)

 

 

Distribution Box)

 

 

 

 

 

 

Frequency

 

 

50Hz or 60Hz, Nominal

 

 

 

 

 

 

 

Waveform

 

 

Sinewave

 

 

Main Mode Overload

>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute

Internal Battery Charger

 

 

 

 

 

Charger Current

 

1.3

2.6

 

 

 

 

 

Battery Parameters

 

 

 

 

 

Type

 

Valve-regulated, non-spillable, lead acid

 

Quantity x V

 

 

20 x 12V

 

 

 

 

 

 

 

 

Battery Mfr. / Part #

5AH battery, CSB HR1221W or YUASA NPH5-12

9AH battery, CSB HR1234W

 

or Panasonic UP-RW1245

 

 

 

 

 

 

Backup Time

See Table 11 - Battery run time, minutes, all models

Recharge Time (Internal

3 hr. to 90% capacity after full discharge into 100% load

 

Batteries)

 

 

 

 

 

Bypass Protection Limits

 

 

 

 

Disable Bypass Operation

If input voltage exceeds ±15% of the nominal voltage

 

 

 

 

 

 

 

Re-Enable Bypass

If input voltage returns to within ±10% of nominal output voltage

 

Operation

 

 

 

 

 

Disable Bypass operation

When the input frequency prevents synchronous operation

 

 

 

 

 

Environmental

 

 

 

 

Operating Temperature,

0 to 40 (32 to 104) see Table 8 - Operating temperature parameters

 

°C (°F)

 

 

 

 

 

Storage Temperature,

 

 

-15 to 50 (5 to 122)

 

 

°C (°F)

 

 

 

 

 

 

 

 

35

Liebert® GXT3

Page 41
Image 41
Emerson 230V, 5000-10, 000-VA user manual Specifications, UPS specifications