Rosemount 708

Device Alert Configuration

Alert Levels

The Rosemount 708 provides 4 user configurable alerts.

Acoustic High - Triggers when acoustic level exceeds a user configured threshold.

Acoustic Low - Triggers when acoustic level falls below a user configured threshold.

Temperature High - Triggers when temperature level exceeds a user configured threshold.

Temperature Low - Triggers when temperature level falls below a user configured threshold.

Alert Setup

There are three methods that can be used to set up these alerts using AMS Wireless Configurator or a field communicator.

Figure 5-3. Alert Setup screen

Alert Setup - Install and Learn

To use the install and learn function on the device to setup the alerts the device must be installed and the equipment being monitored must be in its normal state. After installation and operating conditions have been confirmed, go to the configuration menu under guided setup and click on “alert setup.” This will launch a dialog menu (Figure 5-3 on page 5-3), click on “Install and Learn Alert Setup.” The application will then go through a series of steps that will determine the current input conditions and set alerts based on this normal operation (Figure 5-4).

If the input conditions are too close to the high or low measurement limits of the device, the install and learn function will not be a good method to set the alert levels. If this is the case, it is recommended that installation conditions be checked and that the status is verified before moving ahead. If current input conditions do not allow for the install and learn function, use the manual or guided alert setup to set alerts.