Emerson Attaching Lower Liebert XDCF Module, Locator hole for lower CFunit bottom stud

Models: XDCF

1 28
Download 28 pages 54.34 Kb
Page 13
Image 13
4.3.2Attaching Lower Liebert XDCF Module

Installation

4.3.2Attaching Lower Liebert XDCF Module

Liebert XDCF modules mount on the rear of the Egenera BladeFrame cabinet, near the power mod- ules. The cabinet and Liebert XDCF have prefabricated mounting holes and studs to ease mounting.

1.Set the lower Liebert XDCF module on the left side of the ledge on the rear of the Egenera BladeFrame cabinet. Make sure the positioning stud on the bottom of the Liebert XDCF fits into the locator hole on the ledge as shown in Figure 8.

Figure 8 Locator hole for lower unit stud

Mounting

Figure 8 Locator hole for lower unit stud stud for upper CF unit

Mounting holes for lower CF unit

Locator hole for lower CFunit bottom stud

2.Press the Liebert XDCF against the Egenera BladeFrame cabinet.

3.Insert a panel fastener into the mounting bracket and screw it into the captive panel nut in the rear of the Egenera BladeFrame cabinet. For the hole locations, see Figure 6. Tighten the fasteners securely with a screwdriver, either a blade-type or Phillips.

4.Secure the Liebert XDCF to the cabinet by inserting and tightening four screws along the right side of the Liebert XDCF (see Figure 7).

5.Press the front section of the top deflector against the Egenera cabinet and tighten the panel fasteners joining the two-piece deflector.

NOTE

If a lower module and an upper module will be attached to the Egenera cabinet, proceed to 4.4 - Attaching Upper Liebert XDCF Module.