Piping Connections and Piping Access Points

Figure 16 Profile view of the Liebert XD system

 

Service

 

Valve

Return

Supply

Line

Line

7.Place the protective dust cap and plug back onto both ends of the coupler on the Liebert XDCF and the port pipe.

Figure 17 Piping mains without Liebert XDCF and Liebert XD Flex Pipe

8.Repeat Steps 5 through 7 for the return coupler (larger coupler).

9.Carefully lay the Liebert XD Flex Pipe aside.

NOTICE

Do not fold or bend Liebert XD Flex Pipe. Kinks in the tubing can cause permanent damage to the Liebert XD Flex Pipes.

10.Carefully unbolt the Liebert XDCF from the cabinet.

11.Place the Liebert XDCF on a stable surface.

5.7Insulation

To minimize the possibility of condensation, insulate all piping between the Liebert XDCF and the Liebert XDP or Liebert XDC.

17

Page 21
Image 21
Emerson XDCF user manual Insulation, Return Supply Line