Installation, Operation & Maintenance Manual

MSL600

IP262/Z0, Rev. AB

February 2012

 

 

The transducer may take up to 1 hour to reach thermal equilibrium. Therefore, it may take some time to restore accurate blanket level readings. When the arm tilts out of the supernatant the MSL600 holds the last supernatant temperature reading from the transducer. When the transducer falls back into the supernatant the MSL600 starts to make measurements again.

When the MSL600 measures the supernatant temperature at the transducer, as long as the temperature is within the programmed normal limits for a supernatant then the system uses this measured temperature for speed of sound compensation.

If the measured temperature is outside of these limits then the MSL600 uses the last held temperature reading. This state will continue until a valid temperature reading is again obtained from the transducer in the supernatant.

The upper and lower temperature points are programmable as HMI Engineering parameters. The default values are -5 to +40°C (23 to 104 deg F). The lower temperature should always be less than the upper and valid entries should be limited to temperatures between -40°C and +85°C (-40 to 185 deg F).

Because the tilt switch is sensitive to vibration as well as angle it is de-bounced in software. An engineering parameter exists in the HMI to allow this function to be turned on and off, in the case of for example a particularly vibration prone bridge.

5.9 Digital input

Parameter P340 is used to assign the status of the digital input to an alarm relay if desired. This allows the user to stop measurement whilst the blanket is known to be disturbed and meaningful results would not be obtained. E.g. during high in-flow or when top water level falls below the transducer face and normal measurements can’t be performed.

When the digital input is active all measurements continue as normal and the LED still flashes. The sonar pulse echo display continues to update with live data. However, the blanket level is held at its last value. The trend graph continues to update, relays and current output remain active, and logging continues using the held blanket level.

Digital input active means either a short across the terminals, i.e. from a contact closure or a PLC driving low, i.e. going to ‘0’.

Page 24

Page 24
Image 24
Emerson Process Management MSL600 manual Digital input