7.

Application parameters

 

 

The following section details each parameter.

 

7.1

Main menu parameters

 

 

The following functions are available at the top level of the menu structure.

 

 

 

 

 

 

Note: A full menu structure is shown in section 11.

 

 

7.1.1Cancel password

This is a dynamic parameter; it only appears when password has been opened. This parameter allows the user to cancel the need for password entry before access to parameter editing is allowed.

7.1.2Go Online/Offline

This is a dynamic parameter; it changes according to whether the system is online or offline. The padlock icon will be displayed in a corresponding open or closed state.

7.2 Installation parameters

The following parameters are intended primarily for use during system installation.

7.2.1 Tank Depth – P101

The tank depth is the distance from the front face of the transducer to the bottom of the tank directly under the transducer and is the user programmable range for zero blanket level.

Parameter values (Metric)

 

Parameter values

(Imperial)

Default

Min

Max

Default

Min

Max

7.000m

1.000m

7.000m

23.00 ft

3.30 ft

23.00 ft

7.2.2Xdr Tilt Time – P103

This is the maximum time for which transducer can be out of the water before the system registers a fault. The parameter is either disabled by entering a value of zero or programmed with a value in minutes.

The default is a value of 0 minutes, disabled.

Parameter values:

Default

Min

Max

0 (Disabled)

1

15

7.2.3Tag No. – P242

This is a user defined alpha-numeric parameter. Any string up to 8 characters long may be entered using the keypad. This will usually correspond to the instrument’s asset number or some other such identifier on the user’s schedule.

The following characters are allowed:

!”#$%&’()*+,-./0123456789:;<=>?@ABCDEFGHIJKLMNOPQRSTUVWXYZ[\]^_

Parameter values:

Default

Min

Max

MSL600

-

-