Error Messages and Codes

Generic DAServer error messages and Omron Ethernet-DAServer-specific messages are supported. Use the Log Flag data to customize the messages logged to the Log Viewer. See the Log Viewer online documentation for more information about using log flags.

To troubleshoot DAServer problems, use the following error messages together with the DAServer Manager Diagnostics root data.

DAServer Error Messages

The following table lists all the generic-DAServer and Omron Ethernet-DAServer-specific error messages that are logged to the Log Viewer.

Error Message

Explanation

Probable Cause

Solution

Log Flag

OmronEthAdapter

Windows

Configured invalid

Enter correct

Error

<SockName>: Invalid

Sockets API

Host Name (IP

Host Name or

 

local Host Name (IP

functions do

Addr.) parameter

IP Address.

 

Address)

not accept Host

for SOCKET

 

 

<WrongName>.

Name (IP

<SockName >.

 

 

Further operate with

Address) value.

 

 

 

Host name: 0.0.0.0 !!!

 

 

 

 

 

 

 

 

 

<Socket_

Windows

Configured invalid

Enter correct

Error

ControllerName>:

Sockets API

Controller IP

Controller IP

 

Invalid PLC's

functions do

Address

Address.

 

IPAddress

not accept

<WrongIPAddress

 

 

<WrongIPAddress>

Controller IP

>

 

 

 

Address value.

 

 

 

 

 

 

 

 

Socket <SockName>

Failed creating

For reason - see

Solve

DASProtFail

::OnMessageToSend

Ethernet

Error description in

problems

 

, Creating Eth.

Socket by

the message.

mentioned in

 

Socket get Error

Windows

Most possible

Error

 

<Error number>:

Sockets dlls

cause - Ethernet

description.

 

<Error description>

 

Port already

Avoid

 

 

 

occupied by other

concurrently

 

 

 

OMRON Ethernet

communicatio

 

 

 

DAServer socket or

n through

 

 

 

other application.

Sockets with

 

 

 

 

equal Port

 

 

 

 

numbers.

 

<Socket_

Failed creation

Invalid Watchdog

Enter correct

Error

ControllerName>:

of Watchdog

Address or Invalid

Watchdog

 

Can not create

message.

Watchdog value.

Address (right

 

Watchdog Message.

Watchdog

Watchdog Address

Item name

 

Do not process

message is not

area could be non-

representing

 

Watchdog.

processed until

supported by

2-bytes long

 

 

solving the

current DAServer

Word

 

 

problems.

version.

memory area

 

 

 

 

without

 

 

 

 

suffix). Enter

 

 

 

 

Watchdog.

 