CQM1 PLCs

The following table lists the supported item names for the CQM1 PLCs:

Memory Area

Prefix

Tag

Range

Value

Format

 

 

Type

 

Range

Suffix

 

 

 

 

 

 

IR & SR area

IR

Discrete

IR0:00...IR255:15

0, 1

 

(Bit status)

 

 

or 0.00... 255.15 (**)

 

 

IR & SR area

IR

Integer

IR0... IR255

(*)

u s b f g l

(Word contents)

 

 

or 0... 255 (**)

 

m d e c

LR area

LR

Discrete

LR0:00... LR63:15

0, 1

 

(Bit status)

 

 

 

 

 

LR area

LR

Integer

LR0... LR63

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

HR area

HR

Discrete

HR0:00... HR99:15

0, 1

 

(Bit status)

 

 

 

 

 

HR area

HR

Integer

HR0... HR99

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

AR area

AR

Discrete

AR0:00... AR27:15

0, 1

 

(Bit status)

 

 

 

 

 

AR area

AR

Integer

AR0... AR27

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

Completion flags for

TC

Discrete

TC0... TC511

0, 1

 

Timers/Counters(***)

 

 

 

 

 

Present Values for

PV

Integer

PV0... PV511

(*)

u s b f g l

Timers/Counters

 

 

 

 

m d e c

DM area

DM

Discrete

DM0:0...DM6655:15

0, 1

 

(Bit status)

 

 

 

 

 

DM area

DM

Integer

DM0...DM6655

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

EM area

EM

Discrete

EM0:0...EM6143:15

0, 1

 

(Bit status)

 

 

 

 

 

EM area

EM

Integer

EM0...EM6143

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

 

 

 

 

 

 

Item/point names, corresponding to IR and SR areas, may be without prefix.

(*)Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" ("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default value range for Integer Tag Type is unsigned integer.

(**) Represented memory area available in CQM1H-CPU61 CPU.

(***) Read only

The following examples show the correct format for item names for CQM1 PLCs:

IR2:1

-