CLEARANCES
Clearances (Figures 2, 3 and 4)
When facing the front of the appliance the following minimum clearances to combustible construction must be maintained.
Top of appliance (ceiling) | 24 | inches |
Rear Wall | 2 | inches |
Side Wall | 6 | inches |
Heater Corners (45° angle) to Wall | 4 | inches |
Floor | 0 | inches |
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and proper operation must be provided.
Installation on Rugs and Tile
If this appliance is to be installed directly on carpeting, tile, or other combustible material, other than wood flooring, the appli- ance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the
Figure 3
Figure 2
Figure 4