VENTING FIREPLACE - REAR
To Use the Vent Graph (Figure 29) |
| Venting Graph (Dimensions in Feet) |
1. Determine the height of the center of the |
| REAR EXIT - VERTICAL AND HORIZONTAL TERMINATION |
horizontal vent pipe. Using this dimension on |
| |
| (DIMENSIONS IN FEET) | |
the Sidewall Vent Graph, locate the point it |
| |
| 40 | |
intersects with the slanted graph line. |
| 39 |
2. From the point of this intersection, draw a vertical |
| |
| 38 | |
line to the bottom of the graph. |
| |
| 37 | |
3. Select the indicated dimension, and position the |
| |
unit in accordance with same. |
| 36 |
EXAMPLE A: |
| 35 |
|
| |
If the vertical dimension from the floor of the unit |
| 34 |
is 12 feet, 4 inches the horizontal run to the outer |
| 33 |
wall flange must not exceed 12 feet, 3 inches. |
| 32 |
EXAMPLE B: |
| 31 |
If the vertical dimension from the floor of the unit is |
| 30 |
6 feet, 9 inches the horizontal run to the outer wall |
| 29 |
flange must not exceed 6 feet, 6 inches. |
| 28 |
Special Note: For each 45 degree elbow installed |
| 27 |
in the horizontal run, the length of the horizontal |
| 26 |
run MUST be reduced by 18" (45cm). This does |
|
|
not apply if the 45 degree elbows are installed on |
|
|
the vertical part of the vent system. Reduce 3' for |
|
|
every 90° elbow. |
|
|
Example: According to the chart the maximum |
|
|
horizontal vent length is 20' and if two 45 degree |
|
|
elbows are required in the horizontal vent it must |
|
|
be reduced to 17'. |
|
|
The maximum number of 45 degree elbows |
|
|
permitted per side wall installation is two (2). |
|
|
These elbows can be installed in either the vertical |
|
|
or horizontal run. |
|
|
VERTICALDIMENSIONBOTTOMFROMUNITTHETHEOF TOTHECENTEROUTLETFLUETHEOF | WITHTERMINATIONHORIZONTALVERTICALCAPSOR | A |
| ||
|
| B |
DVP48FP(ONLY) |
| |
REAR HORIZONTAL |
| |
VENT CONNECTION |
|
HORIZONTAL RUN
Figure 29
Acceptable vertical and horizontal vent run.
Unacceptable vertical and horizontal vent run.
Page 19 |