Initial Installation
QUALIFIED INSTALLERS ONLY
Gas Line Connection and Testing:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance. |
|
| |
Manifold | Inlet | ||
GAS LINE CONNECTION | |||
Pressure Tap | |||
Pressure Tap |
• This stove is equipped with a certified flexible pipe |
located on the right side of the unit terminating in a ⅜” |
male NPT fitting. Consult your local authorities codes or |
the CAN/CGA B 149 (1 or 2) installation code in Canada, |
or in the USA gas installations follow either local codes |
or the current edition of the National Fuel Gas Code ANSI |
Z223.1. |
• The efficiency rating of this appliance is a product |
TPTT H TH
T | P |
I | |
OL |
|
IH
OUT
O
L
NI |
|
OF |
|
F |
|
P | |
I | |
L | |
T | O |
NO |
|
thermal efficiency rating determined under continuous |
operating conditions and was determined independently |
of any installed system. |
Pilot Adjustment | Hi/Low | Gas Control |
Screw | Knob | Knob |
Figure 50: Fully Labeled Gas Valve.
The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.45 KPa).
Always check for gas leaks with a soap and water solution after completing the required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
•Turn set screw 1 turn counter clockwise to loosen,
•Place 5/16” (8 mm) I.D. hose over pressure tap system.
•Check pressures using a manometer.
•When finished, release pressure, remove hose & tighten set screw.
Table 7: Pressure and BTU Information.
| Natural Gas | Propane |
Main Burner | #39 DMS | #53 DMS |
Manifold Pressure | 3.8” W.C. / 0.95KPa | 11.0” W.C. / 2.7KPa |
|
|
|
Min. Manifold Pressure | 1.1” W.C. / 0.27KPa | 2.7” W.C. / 0.67KPa |
|
|
|
Max Supply Pressure | 7.0” W.C. / 1.74KPa | 13.0” W.C. / 3.28KPa |
|
|
|
Min. Supply Pressure | 5” W.C. / 1.24KPa | 12.0” W.C. / 2.98KPa |
|
|
|
Max BTU/hr Input | 30,000 BTU/hr (8.80KW) | 26,500 BTU/hr (7.76KW) |
|
|
|
Min. BTU/hr Input | 17,000 BTU/hr (4.98 KW) | 14,000 BTU/hr (4.10KW) |
Venturi Setting | 1/16” min. | 3/16” min. |
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
32