ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls
LonWorks
|
| LonWorks |
|
| Point Description | ||
|
|
|
|
|
| ||
LonWorks Name | SNVT Type | SNVT Index | SCPT Reference | SCPT Index | UCPT Index |
|
|
|
|
|
|
|
| Occupied Cooling Setpoint Input (Read/Write) |
|
|
|
|
|
|
| Standby Cooling Setpoint Input (Read/Write) |
|
nciSetpoints | SNVT_temp_setpt | 106 | SCPTsetPnts | 60 |
| Unoccupied Cooling Setpoint Input (Read/Write) |
|
| Occupied Heating Setpoint Input (Read/Write) | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
| Standby Heating Setpoint Input (Read/Write) |
|
|
|
|
|
|
| Unoccupied Heating Setpoint Input (Read/Write) |
|
nciMinClgSetpt | SNVT_temp_p | 105 |
|
| 4 | Minimum Cooling Setpoint Input (Read/Write) |
|
nciMaxHtgSetpt | SNVT_temp_p | 105 |
|
| 3 | Maximum Heating Setpoint Input (Read/Write) |
|
nvoSpaceTemp | SNVT_temp_p | 105 |
|
|
| Space or Zone Temperature Value (Read Only) |
|
nvoDischAirTemp | SNVT_temp_p | 105 |
|
|
| Discharge Air Temp Field Supplied Only (Read Only) |
|
nvoEffClgSetpt | SNVT_temp_p | 105 |
|
|
| Effective Cooling Setpoint Value (Read Only) |
|
nviSpaceTemp | SNVT_temp_p | 105 |
|
|
| Space or Zone Temperature Value Override(Write) |
|
nvoEffHtgSetpt | SNVT_temp_p | 105 |
|
|
| Effective Heating Setpoint Value (Read Only) |
|
nciAux5LevP | SNVT_lev_percent | 81 |
|
|
| Dehumidification Setpoint (Read/Write) |
|
nciAux1Temp | SNVT_temp_p | 105 |
|
| 147 | Heating Freeze Protection Temperature Setpoint Value (Read/Write) |
|
nciAux2Temp | SNVT_temp_p | 105 |
|
| 148 | Heating Freeze Protection Temperature Setpoint Value (Read/Write) |
|
|
|
|
|
|
| 1st Stage Compressor Heating Output (Read Only) |
|
nvoUnitStatus | SNVT_hvac_type | 112 |
|
|
| 1st Stage Compressor Cooling Output (Read Only) |
|
|
|
| Fan Output (Read Only) |
| |||
|
|
|
|
|
| Unit Mode of Operation (Read Only) |
|
|
|
|
|
|
| Unit Alarm mode (Read Only) |
|
nciPropBand | SNVT_temp_diff_p | 147 |
|
| 177 | Heating/Cooling Prop Band Input (Read/Write) |
|
nciRemoteSetptMin | SNVT_temp_diff_p | 147 |
|
| 98 | Warm/Cool Adjust Span (Read/Write) |
|
nciRemoteSetptMax | SNVT_temp_diff_p | 147 |
|
| 97 | Warm/Cool Adjust Offset Value (Read/Write) |
|
nciTempOffset | SNVT_temp_diff_p | 147 |
|
| 11 | Space or Zone Temperature Sensor Calibration Input (Read/Write) |
|
nviSetpoint | SNVT_temp_p | 105 |
|
|
| General Setpoint Input (Read/Write) |
|
nvoHtgFrzPro1Tmp | SNVT_temp_p | 105 |
|
|
| Heating Freeze Sensing Temperature Value (Read Only) |
|
nvoHtgFrzSetpt | SNVT_temp_p | 105 |
|
|
| Heating Freeze Sensing Temperature Setpoint Value (Read Only) | |
|
|
|
|
|
| Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge | |
|
|
|
|
|
| Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing | |
nvoAlarms | SNVT_lev_cont | 21 |
|
|
| alarm, 8=Faulty Freeze Sensor alarm, | |
|
|
|
|
|
| 9=Loss of Charge] | |
|
|
|
|
|
| (Read Only) | |
nvoPWMOut | SNVT_volt | 44 |
|
|
| ECM PWM Control signal value (Read Only) |
|
nvoECMOvrd | SNVT_volt | 44 |
|
|
| ECM PWM Control signal Override (Read/Write) |
|
nvoHumidity | SNVT_volt | 44 |
|
|
| Space Humidity value (Read Only) |
|
nviAO2 | SNVT_lev_percent | 81 |
|
|
| Spare PWM Output AO2 Command (Write) |
|
nvoAO2 | SNVT_lev_percent | 81 |
|
|
| Spare PWM Output AO2 Value (Read Only) |
|
nciBypassTime | SNVT_time_min | 123 | SCPTbypassTime | 34 |
| Temporary Occupancy Time Period Input (Read/Write) |
|
nvoEffectOccup | SNVT_occupancy | 109 |
|
|
| Effective Occupancy State (Read Only) |
|
nviOccManCmd | SNVT_occupancy | 109 |
|
|
| Occupancy Override Command Input (Read/Write) |
|
nviEmergOverride | SNVT_hvac_emerg | 103 |
|
|
| Emergency Override Input (Read/Write) |
|
nvoFanStatus | SNVT_lev_disc | 22 |
|
|
| Fan Output Status (Read Only) |
|
nvoAccStatus | SNVT_lev_disc | 22 |
|
|
| Accessory 2 Output Status (Read Only) |
|
nvoLP_WVStatus | SNVT_lev_disc | 22 |
|
|
| Accessory 1 Output Status (Read Only) |
|
nvoAlarmStatus | SNVT_lev_disc | 22 |
|
|
| Alarm Output Status (Read Only) |
|
nviAlarmReset | SNVT_lev_disc | 22 |
|
|
| Alarm Reset Input (Read/Write) |
|
nviFanSpeedCmd.StateSNVT | _switch | 95 |
|
|
| Network equivelant of a thermostatic 'G' call. (Write) |
|
nviComprEnable.State | SNVT_switch | 95 |
|
|
| Network equivelant of a thermostatic 'Y1' call. (Write) |
|
nviComprEnable.State | SNVT_switch | 95 |
|
|
| Network equivelant of a thermostatic 'Y2' call. (Write) |
|
nvoRV1Status | SNVT_lev_disc | 22 |
|
|
| Reversing Valve Output Status (Read Only) |
|
nviOccSchedule | SNVT_tod_event | 128 |
|
|
| Occupancy Supervisory Scheduler Command Input (Read/Write) |
|
nvoCompFanProv | SNVT_lev_disc | 22 |
|
|
| Compressor/Fan Proving Switch Status (Read Only) |
|
nvoDirtyFilter | SNVT_lev_disc | 22 |
|
|
| Dirty Filter Switch Status (Read Only) |
|
nvoComp2Status | SNVT_lev_disc | 22 |
|
|
| Compressor Hi Capacity Command Status (Read Only) |
|
nviBO5 | SNVT_lev_disc | 22 |
|
|
| Command for output BO5 used for Emg |
|
nviBO9 | SNVT_lev_disc | 22 |
|
|
| Command for output BO9(Read/Write) |
|
nvoBO5 | SNVT_lev_disc | 22 |
|
|
| Value output for BO5 used for Emg Heat (Read Only) |
|
nvoBO9 | SNVT_lev_disc | 22 |
|
|
| Value output for BO9 (Read Only) |
|
nviDehumEna.State | SNVT_lev_disc | 22 |
|
|
| Dehumidification |
|
36