ENVISION CONSOLE INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wir- ing must be done in accordance with local codes or the National Electric Code, whichever is applicable.
208 Volt Operation
All Envision Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue trans- former wires must be switched.
Microprocessor Remote Thermostat Wiring
Figure 5 | Field | Unit |
| Connections | TB Connections |
|
| R |
| 24 VAC | Red |
| COMMON | C |
| Black | |
|
| Y |
| COMPRESSOR | Yellow |
| REVERSING | O |
| VALVE | Orange |
| FAN | G |
| Green | |
Requires common | LOCKOUT | L |
connections or 24 | SIGNAL | Brown |
|
| |
VAC for activation |
| S |
| SHUTDOWN | |
| Blue | |
| NIGHT | X2 |
| SETBACK | Violet |
|
| X1 |
| LOAD SHED | Pink |
|
| W2 |
Auxiliary Heat Ratings
| Rated | Voltage | Heater | Fan | Heater | Total | Min. | Max. | |
Model | Element | Motor | Element | Unit | Circuit | Fuse/ | |||
Voltage | Min./Max. | ||||||||
| Watts | FLA | FLA | FLA | Amp. | Brkr. | |||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
| 208/60/1 | 197/254 | 2000 | 0.50 | 9.62 | 10.1 | 12.7 | 15 | |
230/60/1 | 197/254 | 2445 | 0.50 | 10.63 | 11.1 | 13.9 | 15 | ||
| 265/60/1 | 239/292 | 2000 | 0.55 | 7.55 | 8.1 | 10.1 | 15 | |
| 208/60/1 | 197/254 | 3000 | 0.69 | 14.42 | 15.1 | 18.9 | 20 | |
230/60/1 | 197/254 | 3668 | 0.69 | 15.95 | 16.6 | 20.8 | 25 | ||
| 265/60/1 | 239/292 | 3000 | 0.65 | 11.32 | 12.0 | 15.0 | 15 |
3/4/08
Always refer to unit name plate data prior to installation.