Image 19
Electrical Connections

ENVISION CONSOLE INSTALLATION MANUAL

Electrical Connections

General

Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wir- ing must be done in accordance with local codes or the National Electric Code, whichever is applicable.

208 Volt Operation

All Envision Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue trans- former wires must be switched.

Microprocessor Remote Thermostat Wiring

Figure 5

Field

Unit

 

Connections

TB Connections

 

 

R

 

24 VAC

Red

 

COMMON

C

 

Black

 

 

Y

 

COMPRESSOR

Yellow

 

REVERSING

O

 

VALVE

Orange

 

FAN

G

 

Green

Requires common

LOCKOUT

L

connections or 24

SIGNAL

Brown

 

 

VAC for activation

 

S

 

SHUTDOWN

 

Blue

 

NIGHT

X2

 

SETBACK

Violet

 

 

X1

 

LOAD SHED

Pink

 

 

W2

Auxiliary Heat Ratings

 

Rated

Voltage

Heater

Fan

Heater

Total

Min.

Max.

Model

Element

Motor

Element

Unit

Circuit

Fuse/

Voltage

Min./Max.

 

Watts

FLA

FLA

FLA

Amp.

Brkr.

 

 

 

 

 

 

 

 

 

 

 

 

 

208/60/1

197/254

2000

0.50

9.62

10.1

12.7

15

09-12

230/60/1

197/254

2445

0.50

10.63

11.1

13.9

15

 

265/60/1

239/292

2000

0.55

7.55

8.1

10.1

15

 

208/60/1

197/254

3000

0.69

14.42

15.1

18.9

20

15-18

230/60/1

197/254

3668

0.69

15.95

16.6

20.8

25

 

265/60/1

239/292

3000

0.65

11.32

12.0

15.0

15