Envision Peripherals IM1609 08 BACNet, Envision Console Controls, Object Identifier, Property

Models: IM1609 10 IM1609 08

1 48
Download 48 pages 7.35 Kb
Page 38
Image 38
BACNet

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

BACNet

 

 

 

 

 

BACnet

 

Point Description

 

Object Identifier

 

Property

Full Reference

Object Type

 

Type Enumeration

Instance

Name

 

Enumeration

 

 

 

Analog Value

 

2

1

Present_Value

 

85

WFI##########.Occupied Cool.Present_Value

Occupied Cooling Setpoint Input (Read/Write)

 

 

 

 

 

 

 

 

 

Standby Cooling Setpoint Input (Read/Write)

 

Analog Value

 

2

2

Present_Value

 

85

WFI##########.Unoccupied Cool.Present_Value

Unoccupied Cooling Setpoint Input (Read/Write)

 

Analog Value

 

2

3

Present_Value

 

85

WFI##########.Occupied Heat.Present_Value

Occupied Heating Setpoint Input (Read/Write)

 

 

 

 

 

 

 

 

 

Standby Heating Setpoint Input (Read/Write)

 

Analog Value

 

2

4

Present_Value

 

85

WFI##########.Unoccupied Heat.Present_Value

Unoccupied Heating Setpoint Input (Read/Write)

 

 

 

 

 

 

 

 

 

Minimum Cooling Setpoint Input (Read/Write)

 

 

 

 

 

 

 

 

 

Maximum Heating Setpoint Input (Read/Write)

 

Analog Input

 

0

1

Present_Value

 

85

WFI##########.Space Temp.Present_Value

Space or Zone Temperature Value (Read Only)

 

Analog Input

 

0

2

Present_Value

 

85

WFI##########.Discharge Air Temp.Present_Value

Discharge Air Temp Field Supplied Only (Read Only)

 

Analog Input

 

0

3

Present_Value

 

85

WFI##########.Effective Clg Setpt.Present_Value

Effective Cooling Setpoint Value (Read Only)

 

Analog Output

 

1

4

Present_Value

 

85

WFI##########.Space temp Ovrd.Present_Value

Space or Zone Temperature Value Override(Write)

 

Analog Input

 

0

4

Present_Value

 

85

WFI##########.Effective Htg Setpt.Present_Value

Effective Heating Setpoint Value (Read Only)

 

Analog Value

 

2

9

Present_Value

 

85

WFI##########.Dehumidify Setpt.Present_Value

Dehumidification Setpoint (Read/Write)

 

Analog Value

 

2

10

Present_Value

 

85

WFI##########.Low Temp Limit Adj.Present_Value

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

 

 

 

 

 

 

 

 

 

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

 

 

 

 

 

 

 

 

 

1st Stage Compressor Heating Output (Read Only)

 

 

 

 

 

 

 

 

 

1st Stage Compressor Cooling Output (Read Only)

 

 

 

 

 

 

 

 

 

Fan Output (Read Only)

 

Multistate Input

 

13

2

Present_Value

 

85

WFI##########.Mode.Present_Value

Unit Mode of Operation (Read Only)

 

 

 

 

 

 

 

 

 

Unit Alarm mode (Read Only)

 

 

 

 

 

 

 

 

 

Heating/Cooling Prop Band Input (Read/Write)

 

Analog Value

 

2

6

Present_Value

 

85

WFI##########.Remote Setpt Span.Present_Value

Warm/Cool Adjust Span (Read/Write)

 

Analog Value

 

2

7

Present_Value

 

85

WFI##########.Remote Setpt Bias.Present_Value

Warm/Cool Adjust Offset Value (Read/Write)

 

Analog Value

 

2

8

Present_Value

 

85

WFI##########.Space Temp Offset.Present_Value

Space or Zone Temperature Sensor Calibration Input (Read/Write)

 

Analog Output

 

1

1

Present_Value

 

85

WFI##########.Space Setpoint.Present_Value

General Setpoint Input (Read/Write)

 

Analog Input

 

0

6

Present_Value

 

85

WFI##########.Water Coil Temp.Present_Value

Heating Freeze Sensing Temperature Value (Read Only)

 

Analog Input

 

0

7

Present_Value

 

85

WFI##########.Low Temp Limit.Present_Value

Heating Freeze Sensing Temperature Setpoint Value (Read Only)

 

 

 

 

 

 

 

 

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge

 

 

 

 

 

 

 

 

Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing

Analog Input

 

0

9

Present_Value

 

85

WFI##########.Alarms Enumerated.Present_Value

alarm, 8=Faulty Freeze Sensor alarm,

 

 

 

 

 

 

 

 

9=Loss of Charge]

 

 

 

 

 

 

 

 

(Read Only)

Analog Input

 

0

8

Present_Value

 

85

WFI##########.ECM Cmd Output.Present_Value

ECM PWM Control signal value (Read Only)

 

Analog Output

 

1

2

Present_Value

 

85

WFI##########.ECM Fan Ovrd.Present_Value

ECM PWM Control signal Override (Read/Write)

 

Analog Input

 

0

5

Present_Value

 

85

WFI##########.Space Humidity.Present_Value

Space Humidity value (Read Only)

 

Analog Output

 

1

3

Present_Value

 

85

WFI##########.AO2 Override.Present_Value

Spare PWM Output AO2 Command (Write)

 

Analog Input

 

0

10

Present_Value

 

85

WFI##########.AO2 Value.Present_Value

Spare PWM Output AO2 Value (Read Only)

 

Analog Value

 

2

5

Present_Value

 

85

WFI##########.Temporary Occ Time.Present_Value

Temporary Occupancy Time Period Input (Read/Write)

 

Multistate Input

 

13

1

Present_Value

 

85

WFI##########.Effective Occupancy.Present_Value

Effective Occupancy State (Read Only)

 

Multistate Output

 

14

1

Present_Value

 

85

WFI##########.Occupancy Command.Present_Value

Occupancy Override Command Input (Read/Write)

 

Multistate Output

 

14

6

Present_Value

 

85

WFI##########.Emergency Override.Present_Value

Emergency Override Input (Read/Write)

 

Binary Input

 

3

1

Present_Value

 

85

WFI##########.Fan Cmd Status.Present_Value

Fan Output Status (Read Only)

 

Binary Input

 

3

6

Present_Value

 

85

WFI##########.Accessory 2 Output.Present_Value

Accessory 2 Output Status (Read Only)

 

Binary Input

 

3

5

Present_Value

 

85

WFI##########.Accessory 1 Output.Present_Value

Accessory 1 Output Status (Read Only)

 

Binary Input

 

3

8

Present_Value

 

85

WFI##########.Alarm Status.Present_Value

Alarm Output Status (Read Only)

 

Multistate Output

 

14

7

Present_Value

 

85

WFI##########.Alarm Reset.Present_Value

Alarm Reset Input (Read/Write)

 

Multistate Output

 

14

2

Present_Value

 

85

WFI##########.Fan Command (G).Present_Value

Network equivelant of a thermostatic 'G' call. (Write)

 

Multistate Output

 

14

3

Present_Value

 

85

WFI##########.Compressor Cmd (Y1).Present_Value

Network equivelant of a thermostatic 'Y1' call. (Write)

 

Multistate Output

 

14

3

Present_Value

 

85

WFI##########.Compressor Cmd (Y2).Present_Value

Network equivelant of a thermostatic 'Y2' call. (Write)

 

Binary Input

 

3

4

Present_Value

 

85

WFI##########.Reversing Valve.Present_Value

Reversing Valve Output Status (Read Only)

 

 

 

 

 

 

 

 

 

Occupancy Supervisory Scheduler Command Input (Read/Write)

 

 

 

 

 

 

 

 

 

Compressor/Fan Proving Switch Status (Read Only)

 

Binary Input

 

3

7

Present_Value

 

85

WFI##########.Dirty Filter (BI-12).Present_Value

Dirty Filter Switch Status (Read Only)

 

Binary Input

 

3

3

Present_Value

 

85

WFI##########.Comp Hi Capacity Cmd.Present_Value

Compressor Hi Capacity Command Status (Read Only)

 

Multistate Output

 

14

8

Present_Value

 

85

WFI##########.Emergency Heat BO5.Present_Value

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

 

Multistate Output

 

14

9

Present_Value

 

85

WFI##########.BO9.Present_Value

Command for output BO9(Read/Write)

 

Binary Input

 

3

9

Present_Value

 

85

WFI##########.BO5 Output.Present_Value

Value output for BO5 used for Emg Heat (Read Only)

 

Binary Input

 

3

10

Present_Value

 

85

WFI##########.BO9 Output.Present_Value

Value output for BO9 (Read Only)

 

Multistate Output

 

14

10

Present_Value

 

85

WFI##########.Dehum Cmd.Present_Value

Dehumidification command-like a Humidistat (Read/Write)

 

37