Envision Peripherals IM1609 08 Multistate Input Type, Multistate Output Type, BACnet Variables

Models: IM1609 10 IM1609 08

1 48
Download 48 pages 7.35 Kb
Page 40
Image 40
Multistate Input (Type 13)

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

BACnet Variables

3:9 BO5 Output

[Read, shows the BO5 (electric heat) output value, Inactive=Off, Active=On]

3:10 BO9 Output

[Read, shows the BO9 output value, Inactive=Off, Active=On]

Multistate Input (Type 13)

13:1 Effective Occupancy

[Read, show the prevailing occupancy status of the heatpump1=Occupied, 2=Unoccupied, 3=Bypass, 255=Invalid]

13:2 Mode Status

[Read, Shows unit status as Auto or Shutdown, 1=Auto, 7=Shutdown]

Multistate Output (Type 14)

14:1 Occupancy Command

[Write, Control the occupancy mode of the heatpump. 1=Occupied, 2=Unoccupied, 3=Bypass, 255=Invalid]

14:2 Fan Command (G)

[Write, allows a network command equivalent of a thermostatic ‘G’ call]

14:3 Compressor Cmd (Y1)

[Write, allows a network command equivalent of a thermostatic ‘Y1’ call]

14:4 Compressor Cmd (Y2)

[Write, allows a network command equivalent of a thermostatic ‘Y2’ call]

14:5 Reversing Vlv Cmd (O)

[Write, allows a network command equivalent of a thermostatic ‘O’ call]

14:6 Emergency Overide

[Write, provide rapid shutdown of the heatpump for fire,etc. 1=Normal, 5=Shutdown]

14:7 Alarm Reset

[Write, Reset lock-out ‘manual reset’ alarms. Alarm conditions must be cleared before a reset can succeed. This variable should be commanded ‘On’ for 20 seconds, then returned to the ‘Off’ condition. 1=Off, 2=On]

14:8 Emergency Heat BO5

[Write, allows a network command for emergency heat, also allows the network to stop automatic emergency heat.]

14:9 BO9

[Write, allow network control of spare output BO9. 1 = Off, 2=On.]

14:10 Dehum Cmd

39

Page 40
Image 40
Envision Peripherals IM1609 08 Multistate Input Type, Multistate Output Type, Envision Console Controls, BACnet Variables