![Unit Operating Parameters](/images/new-backgrounds/34056/3405685x1.webp)
ENVISION CONSOLE INSTALLATION MANUAL
Unit Operating Parameters
Single Speed Models
Entering |
|
|
| Cooling |
|
| ||
Water Flow |
|
|
|
|
|
| ||
Suction | Discharge |
|
|
|
| |||
Water Temp | Water Temp | Air Temp | ||||||
GPM/Ton | ||||||||
°F | Pressure | Pressure | ||||||
| Superheat | Subcooling | Rise °F | Drop °F DB | ||||
|
| PSIG | PSIG | |||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
50 | 1.5 | 127 - 144 | 205 - 225 | 5 - 10 | 10 - 14 | 18 - 22 | 18 - 22 | |
3.0 | 120 - 140 | 185 - 205 | 7 - 15 | 5 - 10 | 8 - 10 | 18 - 22 | ||
| ||||||||
|
|
|
|
|
|
|
| |
70 | 1.5 | 139 - 154 | 280 - 300 | 8 - 11 | 8 | 18 - 22 | 18 - 22 | |
3.0 | 137 - 152 | 250 - 270 | 9 - 12 | 7 - 11 | 8 - 10 | 18 - 22 | ||
| ||||||||
|
|
|
|
|
|
|
| |
90 | 1.5 | 143 - 158 | 360 - 380 | 8 - 11 | 9 - 13 | 18 - 22 | 16 - 20 | |
3.0 | 141 - 156 | 330 - 350 | 9 - 12 | 8 - 12 | 8 - 10 | 16 - 20 | ||
| ||||||||
|
|
|
|
|
|
|
|
Entering |
|
|
| Heating |
|
| ||
Water Flow |
|
|
|
|
|
| ||
Suction | Discharge |
|
| Water |
| |||
Water Temp | Air Temp | |||||||
GPM/Ton | ||||||||
Pressure | Pressure | Temp Drop | ||||||
°F | ||||||||
Superheat | Subcooling | Rise °F DB | ||||||
| ||||||||
| PSIG | PSIG | °F | |||||
|
| |||||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
30 | 1.5 | 73 - 79 | 279 - 304 | 7 - 13 | 2 - 6 | 7 | 18 - 24 | |
3.0 | 79 - 85 | 285 - 310 | 8 - 14 | 2 - 6 | 3 - 6 | 20 - 26 | ||
| ||||||||
|
|
|
|
|
|
|
| |
50 | 1.5 | 103 - 109 | 308 - 333 | 8 - 12 | 4 - 8 | 8 - 11 | 20 - 26 | |
3.0 | 110 - 116 | 315 - 340 | 9 - 13 | 4 - 8 | 4 - 7 | 22 - 28 | ||
| ||||||||
|
|
|
|
|
|
|
| |
70 | 1.5 | 140 - 146 | 330 - 365 | 10 - 14 | 7 - 11 | 11 - 14 | 26 - 32 | |
3.0 | 146 - 153 | 340 - 375 | 10 - 14 | 7 - 11 | 7 - 10 | 28 - 34 | ||
| ||||||||
|
|
|
|
|
|
|
| |
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. |
|
| ||||||
Heating performance based on entering air temperature of 70º F DB. |
|
|
|
Unit Operating Limits
Operating Limits |
| Cooling |
| Heating | ||
|
|
|
|
|
| |
(°F) |
| (°C) | (°F) |
| (°C) | |
|
|
| ||||
|
|
|
|
|
|
|
Air Limits |
|
|
|
|
|
|
Min. Ambient Air | 45 |
| 7.2 | 45 |
| 7.2 |
Rated Ambient Air | 80 |
| 26.7 | 70 |
| 21.1 |
Max. Ambient Air | 100 |
| 37.8 | 85 |
| 29.4 |
Min. Entering Air | 50 |
| 10.0 | 40 |
| 4.4 |
Rated Entering Air db/wb | 80.6/66.2 |
| 27/19 | 68 |
| 20.0 |
Max. Entering Air db/wb | 110/83 |
| 43/28.3 | 80 |
| 26.7 |
|
|
|
|
|
|
|
Water Limits |
|
|
|
|
|
|
Min. Entering Water | 30 |
| 20 |
| ||
Normal Entering Water |
|
| ||||
Max. Entering Water | 120 |
| 48.9 | 90 |
| 32.2 |
|
|
|
|
|
|
|
Notes: |
|
|
|
|
|
|
Minimum/maximum limits are only for