Envision Peripherals IM1609 08 Envision Console Controls, Logic Board DIP Switch Settings

Models: IM1609 10 IM1609 08

1 48
Download 48 pages 7.35 Kb
Page 28
Image 28
Logic Board DIP Switch Settings

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

prevent loss of refrigerant charge and a low suction tem- perature thermistor for freeze sensing. Upon a continuous

30-second measurement of the fault (immediate for high pressure), compressor operation is stopped.

Control Tables for Optional Versatec Microprocessor

Logic Board DIP Switch Settings

Switch

OFF

ON

 

 

 

SW1 - 1

Test - Selected timings sped up to facilitate troubleshooting

Normal - Standard timings

 

 

 

SW1 - 2

Loop - Closed loop freeze sensing setting (15°F)

Well - Open loop freeze sensing setting (30°F)

 

 

 

SW1 - 3

Commercial - Enables NS features when TA32U02 thermostat is used

Normal - Standard thermostat operation

 

 

 

SW1 - 4

IO Display* - Enables Input/Output display on external LED board

Normal* - Unit status display

 

 

 

SW1 - 5

Configures board for 2-speed compressor without fan

Configures board for 2-speed compressor with fan

 

 

 

Normal Control Timing

Blower off delay

30 seconds

 

 

Compressor on delay

10 seconds

 

 

Short cycle delay

5 minutes

 

 

Miniumum compressor on time

2 minutes (except for fault condition)

 

 

High pressure fault recognition delay

Less than 1 second

 

 

low pressure fault recognition delay

30 seconds

 

 

Freeze sensing fault recognition delay

30 seconds

 

 

Condensate overflow fault recognition delay

30 seconds

 

 

Low pressure fault bypass delay

2 minutes

 

 

Freeze sensing fault bypass delay

2 minutes

 

 

Power on delay

5 minutes

 

 

Operational Logic

Mode

Inputs

Fan

Comp

RV

 

 

 

 

 

Htg

Y

ON

ON

OFF

 

 

 

 

 

Clg

Y,O

ON

ON

ON

 

 

 

 

 

Fan

G

ON

OFF

OFF

 

 

 

 

 

Test Control Timing

Blower off delay

5 seconds

 

 

Compressor on delay

2 seconds

 

 

Short cycle delay

15 seconds

 

 

Miniumum compressor on time

5 seconds (except for fault condition)

 

 

High pressure fault recognition delay

Less than 1 second

 

 

low pressure fault recognition delay

30 seconds

 

 

Freeze sensing fault recognition delay

30 seconds

 

 

Condensate overflow fault recognition delay

30 seconds

 

 

Low pressure fault bypass delay

0 seconds

 

 

Freeze sensing fault bypass delay

0 seconds

 

 

Power on delay

15 seconds

 

 

Fault off time

5 minutes

 

 

Diagnostic Modes

 

LED

Current Fault Status

Inputs

Outputs

 

SW1 - #4 On, SW2 On

SW1 - #4 Off, SW2 Off

SW1 - #4 Off, SW2 On

 

 

 

 

 

 

 

Drain

 

Drain pan overflow

Y

Compressor

 

 

 

 

 

Water Flow

 

FS thermistor (loop <15°F, well <30°F)

G

FAN

 

 

 

 

 

High Press

 

High pressure >600 PSI

O

O

 

 

 

 

 

Low Press

 

Low pressure <40 PSI

ES

ES

 

 

 

 

 

Air Flow

 

Not used

NS

NS

 

 

 

 

 

Status

 

Not used

LS

LS

 

 

 

 

 

DHW Limit

 

Not used

Not used

Not used

 

 

 

 

 

HWD

 

SW2 in the On position

Off position

On position

 

 

 

 

 

27

Page 28
Image 28
Envision Peripherals IM1609 08 Envision Console Controls, Logic Board DIP Switch Settings, Normal Control Timing