2.A ICEMAKER INOPERATIVE

YES

IS

“RUN”

“RUN/STOP”

“STOP”

HOPPER

 

FULL?

 

SWITCH

 

 

 

 

?

 

 

NO

 

 

 

 

NORMAL SHUTOFF ON

YES

IS BIN

NO

 

BIN THERMOSTAT.

THERMOSTAT

 

 

 

OPEN

 

1.CHECK THERMOSTAT ADJUSTMENT.

2.REPLACE BIN THERMOSTAT.

PUT SWITCH IN

“RUN” POSITION.

 

IS

 

 

 

IS LOW

 

 

IS HIGH

YES

WATER

YES

 

PRESSURE

NO

PRESSURE

 

SWITCH

 

SWITCH

 

LEVEL NORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN EVAP.?

 

 

 

OPEN?

 

 

OPEN?

 

 

 

 

 

 

20/80 PSI

 

 

448 PSI

 

 

NO

 

 

 

 

NO

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK FOR LOOSE CONNECTION

 

 

 

 

 

 

 

 

 

 

OR BROKEN WIRE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.CHECK THAT WATER SUPPLY IS OPEN.

2.CHECK WATER SUPPLY FILTER.

3.CHECK FOR PLUGGED WATER INLET VALVE.

4.CHECK FOR PROPER TIMING ON TIMERS, IN- CREASE IF LOW WATER LEVEL OBSERVED.

5.CHECK IF DRAINS ARE PLUGGED, KINKED,

OR ARE NOT PROPERLY PITCHED TO AN OPEN TRAP.

1.CHECK FOR REFRIGERANT UNDER- CHARGE.

2.CHECK TXV VALVE.

AIR COOLED UNITS

1.CHECK FOR RESTRICTED AIR FLOW TO AIR CONDENSER.

2.CHECK FOR HOT AIR RECIRCULATING TO AIR CONDENSER. ELIMINATE BY BAFFLING.

3.CHECK FOR DIRTY AIR COOLED CONDENSER.

4.CHECK CONDENSER FAN MOTOR.

5.CHECK FOR REFRIGERANT OVER-CHARGE.

WATER COOLED UNITS

1.CHECK EATER SUPPLY TO CONDENSER.

2.CHECK FOR FAULTY WATER REGULATOR VALVE.

3.CHECK FOR REFRIGERANT OVER-CHARGE.

4.CHECK FOR FOULED CONDENSER.

25