Command/response table for SIS commands
Command ASCII (Telnet) URL Encoded (Web) Response
Relay Functions
Pulse Relay X!*3*X6#
OX! %2A 3%2A
X6# O Cpn
X!•Rly
X%]
Toggle Relay X!*2O X!
%2A 2O Cpn
X!•Rly
X%]
Turn relay ON X!*1O X! %2A 1O Cpn
X!•Rly1]
Turn relay OFF X!*0O X! %2A0O Cpn
X!•Rly0]
View relay status X!
OX! O X%]
Input Contact Closure Port
View the input state or value X! ] X! %5 D X4#]
Firmware Version/Part Number/Information
Query firmware version Q Q X1!]
Query verbose version
information
0Q 0Q sum of responses from 2Q-3Q-4Q]
Query firmware version 1Q 1Q X1!]
Query bootstrap version 2Q 2Q X1!]
Query factory firmware version 3Q 3Q X1! (plus web ver.-desc-UL date/time)]
Query updated firmware version 4Q 4Q X1! (plus web ver.-desc-UL date/time)]
NOTE: An asterisk (*) placed after the version number indicates which version is currently running. A question mark (?) indicates that only the factory firmware version is
loaded. A caret (^) after the version number indicates the firmware version that should be running, but a Mode 1 reset was executed. The default factory firmware
version is loaded. An exclamation point (!) after the version number indicates corrupted firmware.
Request part number N N 60-544-x5]
Request model number 1I 1I IPL T CR48]
Request model description 2I 2I Four contact input ports, Eight relay ports]
Request system memory usage 3I 3I # Bytes/Kbytes used out of # Kbytes]
Request user memory usage 4I 4I # Bytes/Kbytes used out of # Kbytes]
NOTE: X! = Specific port number (01-99)
X% = On/off status: 0 = off/disable; 1 = on/enable
X1!
= Unit firmware version
X4# = 0 = off; 1 = on; value = 4095, based on a 12-bit A to D
X6# = Pulse time in 20 milliseconds per count
IPL T CR48 • Communication and Control 28