Trouble shooting 12 OUTDOOR UNIT Error Method:

Outdoor temp. sensor error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB Outdoor temperature thermistor

Detective details:

When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.

Forecast of Cause :

1. Connector connection failure 2.Thermistor failure 3. Main PCB failure

Check Point 1 : Check connection of Connector

Check if connector is removed.

Check erroneous connection.

Check if thermistor cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

OK

 

 

 

 

 

 

 

 

 

 

Check Pointi t 2 :: Remove connector and check Thermistor resistance value

 

 

 

Thermistor Characteristics (Approx. value)

 

 

 

 

 

 

 

Temperature

 

-20°C

-15°C -10°C

-5°C

0°C

5°C

10°C

 

 

 

(4.0°F)

(5°F)

(14°F)

(23°F)

(32°F)

(41°F)

(50°F)

 

 

 

 

 

 

Resistance Value (k

)

109.0

80.56

60.23

45.40

34.57

26.53

20.56

 

 

Temperature

 

15°C

20°C

25°C

30°C

35°C

40°C

45°C

50°C

55°C

 

(59°F)

(68°F)

(77°F)

(86°F)

(95°F) (104°F)(113°F) (122°F)(131°F)

 

 

Resistance Value (k

)

16.04

12.26

10.00

7.978

6.408

5.184

4.216

3.451

2.841

If Thermistor is either open or shorted, replace it and reset the power.

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

Check Poiintt 3 :: Check voltage of Main PCB (DC5.0V)

 

 

 

 

 

Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)

THERMISTOR

 

(PIPE)

BLACK

 

 

BLACK

 

BLACK

THERMISTOR

BLACK

 

(DISCHARGE)

 

THERMISTOR

(OUTDOOR)

BLACK

BLACK

11

22 CN71

33

44

11

22 CN70

33

If the voltage does not appear, replace Main PCB.

02-14

Page 37
Image 37