8.COMPRESSOR CONTROL

8.COMPRESSOR CONTROL

1.OPEARTION FREQUENCY RANGE

The operation frequency of the compressor is different based on the operation mode as shown in the Table 11.

(Table 11 : Compressor frequency range)

 

Cooling / Dry

Heating

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

 

 

 

 

 

AOU09RL2

18rps

80rps

18rps

120rps

AOU12RL2

96rps

 

 

 

2.OPEARTION FREQUENCY CONTROL AT NORMAL START UP

The compressor frequency soon after the start-up is controlled as shown in the Fig.9. (Fig.9 : Compressor control at start-up)

Frequency

 

 

 

 

 

Frequency

 

 

 

 

 

Frequency

 

 

 

 

 

Frequency

 

 

 

 

 

Frequency

 

 

 

 

 

Frequency

 

 

 

 

 

Time

Time

Time

Time

Time

Time 6

(Frequency)

 

 

 

 

 

Frequency 1.OPEARTION FREQUENCY RANGE Frequency2.OPEARTION FREQUENCY CONTROL AT NORMAL START UP FrequencyManual background FrequencyManual background FrequencyManual background FrequencyManual background

AOU09RL2

56rps

67rps

75rps

78rps

78rps

78rps

AOU12RL2

56rps

74rps

87rps

97rps

108rps

119rps

(Time)

 

 

 

 

 

 

 

Time

Time

Time

Time

Time

Time 6

 

 

 

 

 

 

 

AOU09RL2

80sec

140sec

200sec

380sec

440sec

440sec

AOU12RL2

60sec

100sec

140sec

200sec

350sec

410sec

3.LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE

The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.

(Table12 : Limitation of Compressor Frequency)

[ Cooling/ Dry ]

 

10°C (50°F)

14°C (59°F)

40°C (104°F)

 

 

 

Under

Over

Under

Over

Under

Over

 

 

AOU09RL2

35rps

23rps

-------

30rps

 

 

AOU12RL2

45rps

27rps

 

 

 

 

 

 

 

[ Heating ]

 

 

 

 

 

 

 

 

 

- 3°C (26°F)

7°C (45°F)

14°C (59°F)

40°C (104°F)

 

Under

Over

Under

Over

Under

Over

Under

Over

AOU09RL2

34rps

22rps

27rps

-------

30rps

AOU12RL2

36rps

27rps

27rps

 

 

 

01-08

Page 13
Image 13