Fujitsu ASU12RL2, AOU12RL2 manual Trouble shooting 8 OUTDOOR UNIT Error Method, PFC circuit error

Models: ASU12RL2 AOU09RL2 AOU12RL2

1 62
Download 62 pages 59.61 Kb
Page 33
Image 33
Trouble shooting 8 OUTDOOR UNIT Error Method:

Trouble shooting 8 OUTDOOR UNIT Error Method:

PFC circuit error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB

Detective details:

When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops.

If the same operation is repeated 5 times, the compressor stops permanently.

Forecast of Cause :

1. External cause 2. Connector connection failure 3. Main PCB failure

Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)

PFC circuit error Instant drop : Check if there is a large load electric apparatus in the same circuit.

Manual background Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.

Manual background Noise : Check if there is any equipment causing harmonic wave near electric line.

(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.

Manual background OK

Check Point 2 : Check connection of Connector

Manual background Check if connector is removed.

Manual background Check erroneous connection.

Manual background Check if cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

Manual background OK

Check Point 3 : Replace Main PCB

Manual background If Check Point 1, 2 do not improve the symptom, change Main PCB.

02-10

Page 33
Image 33
Fujitsu ASU12RL2 Trouble shooting 8 OUTDOOR UNIT Error Method, PFC circuit error, Detective Actuators, Detective details