Trouble shooting 8 OUTDOOR UNIT Error Method:

PFC circuit error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB

Detective details:

When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops.

If the same operation is repeated 5 times, the compressor stops permanently.

Forecast of Cause :

1. External cause 2. Connector connection failure 3. Main PCB failure

Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)

Instant drop : Check if there is a large load electric apparatus in the same circuit.

Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.

Noise : Check if there is any equipment causing harmonic wave near electric line.

(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.

OK

Check Point 2 : Check connection of Connector

Check if connector is removed.

Check erroneous connection.

Check if cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

OK

Check Point 3 : Replace Main PCB

If Check Point 1, 2 do not improve the symptom, change Main PCB.