3. Defrost Flow Chart

The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.

Heating operation start : Compressor ON

(Not defrosted for 10 minutes)

Normal defrost

Integrating defrost

Outside air temp. > -10°C= (14°F)

Outdoor HEX temp.

Below - 17°C(1.4°F)

Outside air temp. < -10°C(14°F)

Outdoor HEX temp.

-Outside air temp. Below - 7°C(-44.6°F) or

Outdoor HEX temp. Below - 20°C(-4°F)

Intermittent

operation

Continuous operation

 

 

 

 

 

 

 

 

Compressor

 

Compressor

 

Compressor

 

OFF count :

 

integrating

 

integrating

 

40 times

 

operation:

 

operation:

 

(Less than 10min.)

 

Over 240 min.

 

Over 213 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

Outdoor

 

 

 

 

heat exchanger

 

heat exchanger

 

 

 

 

temperature:

 

temperature:

 

 

 

 

Below - 3°C

 

Below - 5°C

 

 

 

 

(26.6°F)

 

(23°F)

 

 

 

 

 

 

 

 

Defrost start

Defrost Indicator: [Operation lamp]

7 sec ON / 2 sec OFF

Outdoor fan : OFF

Compressor speed : 0 rps

4-way valve : OFF

Compressor speed : 90rps

Outdoor HEX temp.: Over 16°C (60.8°F)

or

Compressor ON time: Maximum 15 minutes

Defrost end